32
8.2.3
Settings for temperature monitoring
8.2.3.1
Configure limit value monitoring with OUT2
SEL2
TEMP
Select and
set.
OU2
Select and set switching function.
Hno
= Hysteresis function / normally open
Hnc
= Hysteresis function / normally closed
Fno
= Window function / normally open
Fnc
= Window function / normally closed
SP2
Select and set value where output switches.
rP2
Select and set value where output switches back.
8.2.3.2
Configure analog value for temperature
SEL2
TEMP
Select and
set.
OU2
Select and set function.
I
= Temperature-proportional current signal (4…20 mA)
ASP
Select and set value where the
minimum value
is displayed.
AEP
Select and set value where the
maximum value
is displayed.
8 Progr Parameter setting