background image

0507347110/160114/B SHIELD fire safety solutions (5k1)

| USER | EN - 25

18.1 In case of fire

When a fire is detected, the system can be activated manually 
through the manual call point (refer to paragraph 17.2). 
Automatic detection of fire is triggered by heat, sparks or 
smoke. 

In the event of a fire, the system reacts as follows.

1. Display shows 

ALARM

 and indicates fire zone. 

2. Red alarm LED in specific zone flashes. Audible/visible 

indicators are switched on and the fire alarm sounder is 
activated. 

3. System control panel stops fan, closes sliding valves and 

releases compressed air through 3/2 solenoid valve.

4. Five seconds after fire alarm the FlameShield fire 

extinguishing generator(s) is/are activated; LEDs 

OUTPUT 

TO 

4

 will be lit. 

18.2 Post-fire procedure

Silence fire alarm sounder. Refer to paragraph .

18.2.1 MDB + FlameShield 

After any fire incident, the entire installation must be 
inspected and released by a skilled and authorized 
service engineer. 

        

The following activities are strictly reserved to skilled 
and authorised service engineers. 

Inspect the filter and hopper for glowing materials before 
starting maintenance. 

Inspect the MDB filter cartridges and replace in case of 
doubt, when they are damaged by fire or any cartridge at 
less than 50 cm (20 in.) proximity of the aerosol release 
opening of the FlameShield generator. 

Follow maintenance procedure on spark detectors (ref. 
paragraph 7.5).

Follow maintenance procedure on smoke detector (ref. 
paragraph 8.5).

Disconnect the ShieldControl panel.

Replace the FlameShield module(s). 

Perform the post installation checks of all separate 
components as described in the relevant paragraphs.

Go through the commissioning checklist as described in 
chapter 12. 

The used FlameShield modules can be disposed of as non-
hazardous waste.

18.2.2 Manual call point

Reset manual call point. Refer to paragraph 17.2.1.

18.3 Release

Release of the system after fire is strictly reserved to skilled and 
authorized personnel. 
   

18

FIRE ACTION PROCEDURE

WARNING!

Always comply with the legal fire safety procedures 
and respect instructions from the fire safety 
coordinator. 

ATTENTION!

The FlameShield extinguishing material is extremely 
fine. In case of fire, it may seem like smoke escapes 
through the seams of the filter system, but most 
probably it concerns the extinguishing material which 
is fully harmless to environment and human. 

WARNING!

To avoid re-ignition of the fire and to prevent 
consequential damage, keep filter closed for at least 
15 minutes. 

WARNING!

During inspection and maintenance, always use 
Personal Protective Equipment (PPE) to avoid injury. 
This also applies for persons who enter the work area.

ATTENTION!

Do 

not

 start maintenance before receiving permission 

from authorized personnel. 

CAUTION!

The FlameShield modules get hot from the release of 
the aerosol. Allow the modules to cool down before 
replacement or use protective gloves.

Summary of Contents for Shield 5k1

Page 1: ...www plymovent com EN Fire safety solutions EN Installation and user manual shield 5k1...

Page 2: ...general convenience of our clients It has been based on general data pertaining to construction material properties and working methods known to us at the time of issue of the document and is therefo...

Page 3: ...B ranging from MDB 4 to MDB 48 other sizes on request central fan type SIF system control panel SCP round ductwork of the appropriate diameter 1 3 Functional description of SHIELD fire safety solution...

Page 4: ...after activation thus preventing re ignition The amount of aerosol is proportional to the filter volume and can be easily adapted by adding generators The system control panel SCP M controls the filte...

Page 5: ...cifications given in this installation manual must not be altered Modifications Modification of parts of the product is not allowed Product combinations Since the products are used in combination with...

Page 6: ...es off fan motor is switched off release of compressed air through solenoid valve After a delay of 5 seconds sliding valves close release of aerosol by FlameShield generators during 60 seconds After a...

Page 7: ...nect the FlameShield module s Make sure the panel is in RUN mode 5 1 Product description and operation ShieldControl 5k1 is a fire detection panel1 with a separate manual call point It has three detec...

Page 8: ...the mains in accordance with the electrical diagram on page 29 5 5 Maintenance The ShieldControl panel itself does not require specific maintenance except for cleaning Do not use solvents or detergent...

Page 9: ...10 160114 B SHIELD fire safety solutions 5k1 INSTALLATION EN 8 Fig 5 1 5 6 4 Reset Refer to paragraph 17 2 1 on page 24 for the reset procedure NC NO field wiring toggle switch white red terminal stri...

Page 10: ...sets of temperature detectors must be wired in parallel The detectors act as one sensor and are connected to Zone 2 ref electrical diagram on page 29 End of line resistor REOL The last detector that...

Page 11: ...status ShieldControl should indicate a fire in Zone 2 To perform the test proceed as follows Observe the functional testing instructions as described in paragraph 4 4 Functionally test all heat detect...

Page 12: ...t of the tool Push the flange completely through the hole in the duct and insert the split washer by rotating it into the inside of the duct Gently pull the flange back through the hole with the inser...

Page 13: ...having local jurisdiction Cleaning intervals differ per situation and regular checks need to be performed to set the cleaning interval for your specific situation To clean and test the spark detectors...

Page 14: ...mount the smoke detector proceed as follows Drill a hole 51 mm 2 in in the duct at the intended mounting position Determine the correct tube length according to the table below Fig 8 2 Remove the end...

Page 15: ...the supplied self tapping screws The arrow on the mounting bracket must correspond with the airflow direction through the duct Fig 8 4 Post installation checks Check that all screws are tightened Che...

Page 16: ...LEDs extinguishes at the same time Place the cap back on the test opening 8 5 Maintenance The sensor wil become polluted over time When the sensor is 75 contaminated it must be replaced This is indic...

Page 17: ...ed locally connection wire 5 x 20 AWG cable Wiring Connect the sliding valves to the system control panel SCP in accordance with the electrical diagram on page 29 Connect the reed contacts to the syst...

Page 18: ...er the fire alarm Post installation checks Check electrical connections Check pneumatic connections Check bolts and nuts for correct tightening 9 5 Functional test The sliding valves can be tested man...

Page 19: ...main compressed air line between pressure reducer and filter unit It is recommended to mount the valve on the filter housing Mount the solenoid valve at an appropriate position 10 3 Electrical connect...

Page 20: ...lation position of FlameShield must be as follows Fig 11 1 A Filter cartridge B Junction box C Framework MDB D Mounting bracket FlameShield E FlameShield module Fig 11 1 To install the FlameShield mod...

Page 21: ...A true functional check can be done by replacing the FlameShield module with the detonation simulator supplied and create a fire condition e g by removing one of the spark detectors After fire alarm t...

Page 22: ...in RUN mode 6 Test the detectors and system control panel SCP as instructed to make sure that the system is reacting as expected and required 7 Reset the panel detectors and system control panel SCP...

Page 23: ...functionally tested through exposure to daylight and the signal being monitored by ShieldControl Check OK 1 Is the smoke detector placed in the filter outlet duct 2 Is the mounting bracket correctly i...

Page 24: ...sed 3 Is the solenoid functionally tested after a fire test alarm in the complete system set up Check OK 1 Are FlameShield modules undamaged 2 Is the correct number of FlameShield modules being instal...

Page 25: ...s Reset alarm condition Determine cause e g fire and only push SYSTEM RESET after cause has been settled Panel will go to normal and display will show SYSTEM OK Program switch in RUN This action will...

Page 26: ...maintenance procedure on spark detectors ref paragraph 7 5 Follow maintenance procedure on smoke detector ref paragraph 8 5 Disconnect the ShieldControl panel Replace the FlameShield module s Perform...

Page 27: ...d After the life of the product dispose it of in accordance with federal state or local regulations activated FlameShield generators can be disposed of as non hazardous waste non activated FlameShield...

Page 28: ...in a particular environment and to perform a specific task The entire installation must comply with the relevant directives and standards The assembly instructions given by the manufacturer as well as...

Page 29: ...MDB 8 V MDB 8 H MDB 10 1x FS 200 1x FS 200 1x FS 500 1x FS 500 1x FS 500 MDB 4 MDB 12 MDB 12 V MDB 12 H MDB 16 MDB 16 H MDB 16 V 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 MDB 20 MDB...

Page 30: ...SHIELD fire safety solutions 5k1 ELECTRICAL DIAGRAM 29 Electrical diagram 900010G0026 0 22 05 2014...

Page 31: ......

Page 32: ...www plymovent com 0507347110 160114 B SHIELD 5k1 EN...

Reviews: