0507347110/160114/B SHIELD fire safety solutions (5k1)
| GENERAL | EN - 5
The fire suppression system can be
activated in two ways:
- automatically by heat, sparks and/
or smoke detectors
- manually at manual call point
If there is a fire, the automatic
sequence of events is as follows:
- acoustic fire alarm goes off
- fan motor is switched off
- release of compressed air through
solenoid valve
After a delay of ± 5 seconds:
- sliding valves close
- release of aerosol by FlameShield generators during 60
seconds
After activation, the FlameShield aerosol remains active for at
least 30 minutes to prevent re-ignition of the fire. In this way,
damage to the filter installation, as well as consequential loss is
kept to a minimum.
3
OPERATION IN CASE OF FIRE
WARNING!
All staff must be familiar with the fire procedures.