0507347110/160114/B SHIELD fire safety solutions (5k1)
| INSTALLATION | EN - 18
10.1 Product description and operation
Fig. 10.1
Normally closed 3-way 2-position solenoid valve.
When the connected filter system is in operation, the solenoid is
activated and compressed air is supplied to the cleaning system
of the filter (port P and A are open). If there is a fire alarm or
power failure, the solenoid will return to its normally closed (NC)
position, closing port P and opening port R. In this position
compressed air escapes from the filter and it is unable to
execute a filter cleaning procedure. This prevents fresh oxygen
from reaching the filter in case of fire.
Fig. 10.1
10.2 Installation
Location
The solenoid valve is placed in the main compressed air line
between pressure reducer and filter unit. It is recommended to
mount the valve on the filter housing.
•
Mount the solenoid valve at an appropriate position.
10.3 Electrical connection
To be sourced locally:
- connection wire: 5 x 20 AWG
Wiring
•
Connect the solenoid valve to the system control panel SCP
in accordance with the electrical diagram on page 29.
10.4 Compressed air connection
The solenoid valve is fitted with a 12 mm compressed air tube
connection.
•
Connect the solenoid valve to compressed air.
•
Check compressed air connection of filter system.
10.5 Functional test
The solenoid valve is provided with a button for testing
purposes.
•
Press button (A) and check that the compressed air escapes
from outlet R (B).
Fig. 10.2
10
SOLENOID VALVE
Scope of supply:
- 3/2 solenoid valve, incl.
electrical entry terminal,
2 swivel elbow adapters
and silencer
- screw M4x35 (2)
- washer M4 (2)
- locknut M4 (2)
A
P
R
A
P R
A
P
R
A
B