400-480V
600V
Fig.3
Fig.4
0000100519/121212/0 MDB-2X/2F/4F
EN - 12
0
4
usE
4.1
Function MDB-2F/2X
Functions of the
MDB-2F
filter unit:
A
Manual start/stop ventilator with delayed off
B
Optional remote start/stop ventilator with delayed off
C
Automated on line filter cleaning
D
Automated off line filter cleaning
E
Manual on and off line filter cleaning
F
Alarm signal (optical and acoustical) for:
-
Tripped overload relay
-
Absence of compressed air (only during cleaning cycle)
-
Clogged filter
G Reset Alarm
4.2
Operation
start/stop FAN
The ventilator is started and stopped with the Start/Stop FAN
push button or with the remote Start/Stop. The Start/Stop
FAN push button has a delayed off of 1 second. The remote
Start/Stop has a delayed off of 2 minutes.
reset Alarm
The reset alarm push button can be used to reset the alarm
after the filter cleaning system has failed to clean the filters
after 1 hour. In this case the filters must be replaced
immediately, otherwise the alarm will sound again after one
hour.
Manual on and off line filter cleaning
The Reset Alarm push button can also be used to start a
manual cleaning cycle (2 pulses per valve).
• To start a cycle, keep the Reset Alarm push button
pressed for minimum 5 seconds.
4.3
Function MDB-4F
Functions of the
MDB-4F
filter unit:
A
Manual start/stop ventilator with delayed off
B
Optional remote start/stop ventilator with delayed off
C
Adjustable ventilator speed with potentiometer on the
frequency converter or in case of 600V with
potentiometer connected to frequency converter.
D
Automated on line filter cleaning
E
Automated off line filter cleaning
F
Manual on- and offline filter cleaning
G Alarm signal (optical and acoustical) for:
-
Error frequency converter
-
Absence of compressed air (only during cleaning cycle)
-
Clogged filter
H Reset Alarm
4.4
Operation
start/stop FAN
The ventilator is started and stopped with the Start/Stop FAN
push button or with the remote Start/Stop. The Start/Stop
FAN push button has a delayed off of 1 second. The remote
Start/Stop has a delayed off of 2 minutes.
reset Alarm
The reset alarm push button can be used to reset the alarm
after the filter cleaning system has failed to clean the filters
after 1 hour. In this case the filters must be replaced
immediately, otherwise the alarm will sound again after
1 hour.
Manual on and off line filter cleaning
The Reset Alarm push button can also be used to start a
manual cleaning cycle (2 pulses per valve). To start a cycle,
keep the Reset Alarm push button pressed for minimum
5 seconds.
Ventilator speed adjustment
The speed of the ventilator can be adjusted with the
potentiometer on the frequency converter in the control
panel. The adjustment range is from 20 – 50 Hz.
Alarm buzzer
Reset alarm Push
button
Start/Stop fan
Push button
System failure
red light
Power on
white light
Fan running
green light
Summary of Contents for MultiDust BANK 2F
Page 40: ...0000100519 121212 0 MDB 2F 2X 4F 390...
Page 41: ...0000100519 121212 0 MDB 2F 2X 4F 400...
Page 42: ...0000100519 121212 0 MDB 2F 2X 4F 410...
Page 43: ...0000100519 121212 0 MDB 2F 2X 4F 420...
Page 44: ...0000100519 121212 0 MDB 2F 2X 4F 430...
Page 45: ...0000100519 121212 0 MDB 2F 2X 4F 440...
Page 46: ...0000100519 121212 0 MDB 2F 2X 4F 450...
Page 47: ...0000100519 121212 0 MDB 2F 2X 4F 460...
Page 48: ...0000100519 121212 0 MDB 2F 2X 4F 470...
Page 49: ...0000100519 121212 0 MDB 2F 2X 4F 480...
Page 50: ...0000100519 121212 0 MDB 2F 2X 4F 490...
Page 51: ...0000100519 121212 0 MDB 2F 2X 4F 500...
Page 52: ...www plymovent com 0000100519 121212 0 MDB 2X 2F 4F...