Sec.
Prim.
1
2
3
4
5
6
7
8
0000100519/121212/0 MDB-2X/2F/4F
EN - 8
0
4
iNstAllAtiON
Installation of the
MDB-2F/2X
4.1
tools and requirements
No special tools required.
4.2
unpacking
The package should contain:
-
Filter unit
MDB-2F/MDB-2X
-
Precoat material (in the dust bin)
-
Handle for dust bin lifting device
If parts are missing or damaged, contact your supplier.
4.3
installation measurement
See illustration below.
4.4
Electric connection
Connect the
MDB-2F/MDB-2X
in accordance with electric
diagram 0517001110 1 of 2 and 0517001110 2 of 2.
AttENtiON
All electrical wiring which includes primary,
secondary and control wiring must be done by
certified/licensed electrician.
wArNiNg!
ELECTROCUTION HAZARD.
Disconnect mains before servicing. Failure to do so
could result in serious personal injury or death.
wArNiNg!
Do not attempt installation of this unit unless you
are familiar with the necessary tools, equipment,
utility connections and potential hazards.
Installation should be performed only by a
qualified service provider. Failure to do so could
result in reduced performance of the unit, serious
personal injury or death.
A line supply
See diagram 0517001110.
B Transformer wiring
Check that rated voltage corresponds with supply voltage to
avoid damage to electrical components. Set the transformer
on the primary voltage connection to the correct voltage
position. Fig.1 and 2.
C Motor wiring
The motor wiring has to be reconfigured according to the
corresponding voltage diagram on the motor nameplate or
inside the connection box cover.
D changing and adjusting the thermal overload
The thermal overload needs to be exchanged for a version
suited for a higher current at 240V, an extra thermal
overload for 240V/60Hz/3-ph supply is delivered as standard
and can be found in the ”Power control box”.
The thermal overload current must be adjusted according to
the nominal current on the motor name plate. To compensate
for line supply fluctuations, set the dial on the thermal
overload 10-20% higher than the nominal motor current.
4.6
control circuit
Remote Start/Stop or External switch.
See diagram 0517001110 is wired to terminal block X1 on
positions 7 and 8.
0
120V (2) white
208V (3) brown
240V (4) violet
277V (5) orange
400V (6) blue
480V (7) grey
600V (8) black
(1) yellow
P1
P2
P3
P4
P5
P6
P7
red (10)
green (9)
S1
230V 30VA
Uo= 237,0V
S1 and S2 cannot be loaded
at the same time
blue (12)
brown (11)
S2
120V 30VA
Uo= 123,6V
violet (14)
orange (13)
S3
U= 24V
35VA
Uo= 27,9V
50-60 Hz
Fig.1
Fig.2
1172
*
*
Total length
MDB-2X
* Dimensions for
MDB-2F
*
1645
Outlet
MDB
-2x
4.5
Power Circuit
The
MDB-2F
default supply voltage is 400V/50Hz/3-ph or
480V/60Hz/3-ph. If only a supply voltage of 240V/60Hz/3-ph
is available, please follow steps B to D.
Summary of Contents for MultiDust BANK 2F
Page 40: ...0000100519 121212 0 MDB 2F 2X 4F 390...
Page 41: ...0000100519 121212 0 MDB 2F 2X 4F 400...
Page 42: ...0000100519 121212 0 MDB 2F 2X 4F 410...
Page 43: ...0000100519 121212 0 MDB 2F 2X 4F 420...
Page 44: ...0000100519 121212 0 MDB 2F 2X 4F 430...
Page 45: ...0000100519 121212 0 MDB 2F 2X 4F 440...
Page 46: ...0000100519 121212 0 MDB 2F 2X 4F 450...
Page 47: ...0000100519 121212 0 MDB 2F 2X 4F 460...
Page 48: ...0000100519 121212 0 MDB 2F 2X 4F 470...
Page 49: ...0000100519 121212 0 MDB 2F 2X 4F 480...
Page 50: ...0000100519 121212 0 MDB 2F 2X 4F 490...
Page 51: ...0000100519 121212 0 MDB 2F 2X 4F 500...
Page 52: ...www plymovent com 0000100519 121212 0 MDB 2X 2F 4F...