background image

Pizzato Elettrica Srl
via Torino, 1
36063 MAROSTICA (VI)
ITALY

e-mail: [email protected]
web site:  www.pizzato.com

Phone:   +39.0424.470.930

ZE FOG147B22-EU

4/18

 1 INFORMATION ON THIS DOCUMENT

1.1 Function

The present operating instructions provide information on installation, connection and 
safe use for the following articles: 

CS MP312•0.

1.2 Target audience

The operations described in these operating instructions must be carried out by quali-
fied personnel only, who are fully capable of understanding them, and with the techni-
cal qualifications required for operating the machines and plants in which the safety 
devices are to be installed.

1.3 Application field

These instructions apply exclusively to the products listed in paragraph Function, and 
their accessories.

1.4 Original instructions

The Italian language version is the original set of instructions for the device. Versions 
provided in other languages are translations of the original instructions.

 2 SYMBOLS USED

 This symbol indicates any relevant additional information

 Attention: Any failure to observe this warning note can cause damage or mal-

function, including possible loss of the safety function.

 3 DESCRIPTION

3.1 Device description

The safety device described in this manual is defined according to the Machinery 
Directive 2006/42/EC as logic component for safety functions.
This multifunction safety module is used to implement safety functions such as emer-
gency stop monitoring, door or guard control, monitoring safety barriers, safety mats 
or magnetic sensors on industrial machines. This device is particularly suitable for 
controlling machines with a variety of combined safety functions (for example, simul-
taneous emergency stop and guard control), or machines with parts that have to be 
isolated in normal operating conditions (to do maintenance for example).

3.2 Device functions

This multifunction safety module has many different inputs, which are evaluated by an 
application program to activate safety or signalling outputs. To reach the highest levels 
of safety, this device has a redundant and self monitoring structure with two proces-
sors that continuously check the system in a coordinated way. The module also has 
numerous green LEDs that show the state of the inputs and outputs and two red/blue 
LEDs (P1, P2) that show the state of the processors or any faults.
In the safe state, the safety outputs are switched off (safe power off).
The safety function performed by the module is set up and configured using the logical 
blocks available in the Gemnis Studio configuration software, which is distributed as 
freeware by Pizzato Elettrica and which must be installed on an external PC. A general 
safety function can be defined as follows:
- the safety outputs are switched off within the specified reaction time if the result of 

the programmable logic solver (application program) is negative or in the case of 
errors.

On the basis of external device features and the circuit structure, with this module you 
can obtain safety circuits up to:
- SIL 3 acc. to EN 62061;
- PL e acc. to EN ISO 13849-1:2015;
- safety category 4 acc. to EN ISO 13849-1:2015.

3.3 Intended use of the device

- The device described in these operating instructions is designed to be applied on 
industrial machines.
- The direct sale of this device to the public is prohibited. Installation and use must be 
carried out by qualified personnel only.
- The use of the device for purposes other than those specified in these operating 
instructions is prohibited.
- Any use other than as expressly specified in these operating instructions shall be 
considered unintended by the manufacturer. 
- Also considered unintended use:
a) using the device after having made structural, technical, or electrical modifications 
to it;
b) using the product in a field of application other than as described in paragraph 
TEChNICAL DATA.

 4 OPERATION

4.1 Definitions

- Application program: the part of the internal safety module software intended for the 

customer's application.

- POwER ON: the safety module state, which lasts from the power on until the end of 

the internal controls.

- RUN: the safety module state on completion of the POwER ON phase (if no errors 

have been detected) in which the application program is run.

- ERROR: the safety module state when a fault is detected. In this state, the module 

switches to the safe state, i.e., all safety outputs are deactivated.

- Fault: a fault can be internal or external to the safety module. Internal faults are 

autonomously detected thanks to its redundant and self-monitored structure. An 
external fault can be detected by the application program. It follows that the definition 
of external fault is strictly dependent on the application (see note A).

4.2 Description of operation

when supplied with power, the module enters the POwER ON state and runs an inter-
nal self-diagnosis. In this phase, the two processor LEDs (P1, P2) remain illuminated 
red for about 1 second. If the internal tests are completed without malfunction, the 
two LEDs are switched off, the module enters the RUN state, and runs the application 
program. If the start tests are not passed, the module enters the ERROR state and the 
malfunction is indicated by the processor LEDs (P1, P2) remaining illuminated in red.

The green LEDs relating to the power supply and the module inputs are not controlled 
by processors, and they immediately begin indicating the states of the respective in-
puts/outputs.
when the module is in the RUN state, and no faults are detected, the two LEDs (P1, 
P2) remain switched off.

In the RUN state, the module can detect faults external to the module, for example 
caused by short circuits, or invalid input states (see note A). Depending on the fault 
type detected, the application program may place the module in ERROR state, to 
indicate the malfunction. In this case, the application program can communicate an 
error code by making the LEDs (P1, P2) flash in sequence.
During the Run state, simultaneously with application program execution, the module 
constantly runs a series of internal tests to check for correct hardware operation. If a 
malfunction is detected, the module state changes to ERROR.

Once in ERROR state, the module is placed in a safe condition, that is with all the 
safety outputs open; the application program is no longer evaluated, and neither are 
the system inputs. Furthermore, the semiconductor signalling outputs are left unal-
tered (changes in inputs do not affect them) at the value imposed by the application 
program before entering the ERROR state. To reset the module, just switch it off for the 
required duration (see technical data) and then switch it on again.

Note A:

 A short circuit is not always a fault. For example, in the case of an ordinary push button for 

emergency stops equipped with two NC contacts, contact opening is the signal to be evaluated and 
a short circuit between the two contacts is a fault. In contrast, in the case of a safety mat with 4-wire 
technology, the opposite is true, i.e. a short circuit between the wires is the signal to be evaluated 
whereas wire interruption is a fault.

4.3 Wiring diagrams
4.3.1 Safe detection of rotating axes motion (up to 2 axes)

F1B

A4

F1A

CS MP312

0

A3

+

-

F2B

F2A

axis1

axis 2

LED F•A

LED F•B

Description

/

/

No supply voltage on the module.

green

green

Module starting phase

orange

orange

Internal tests upon start-up.

green

*

The sensor connected to terminal F•A has been detected as active.

*

green

The sensor connected to terminal F•B has been detected as active.

blinking  

green

blinking  

green

When the axes are rotating, LEDs F•A and F•B blink green with 

the same frequency as the signal received at the proximity sensor 
inputs, and the voltage detected at terminals A3-A4 is correct.

red / green,  

alternating

red / green,  

alternating

The voltage detected at terminals A3-A4 is not within the allowed 
range (e.g.: terminal detachment, faulty sensors).

red

 red

Internal board error.

Legend: 

 

/ = off;  

* = indifferent

- Only PNP-type proximity sensors can be used.
- The duty cycle of each cam must be such that at least one of the two sensors is 

always active.

- To avoid sensor activation errors, adopt suitable assembly procedures to prevent 

foreign bodies getting between the proximity sensors and the cams.

- Fit the two proximity sensors of the same axis so they are mechanically independent 

of each other. This prevents a simultaneous failure of both sensors. Don’t fix both 
sensors to the same bracket for example.

- To detect the direction of rotation, the two sensors of the same axis must be mounted 

with an angle of less than 90°, while guaranteeing at least one sensor is always ac-
tive during axis rotation, as this requirement must be met. Suggested value: 30-50°.

- The direction of rotation of each axis must be checked on the machine to make sure 

it is correct, as this depends to a great extent on:
- axis acceleration and angular velocity;
- the angular offset between the sensors;
- cam design (duty cycle);
- the reaction time of the sensors used.

Summary of Contents for CS MP312-0

Page 1: ...un guasto In questo stato il modulo si pone in condizioni di sicurezza ossia con tutte le uscite di sicu rezza disattivate Guasto un guasto pu essere interno o esterno al modulo di sicurezza I guasti...

Page 2: ...eb Pizzato Elettrica Questo dispositivo deve essere installato ed usato solamente se tutte le presenti istruzioni tecniche e tutte le norme di sicurezza rilevanti per l applicazione sono state osserva...

Page 3: ...indicate fanno riferimento ai morsetti di alimentazione Ax vedi caso per caso ogni modulo della scheda dove sono presenti i morsetti di tipo Fx 9 7 Circuiti di ingresso disaccoppiati Jx Numero ingress...

Page 4: ...are deactivated Fault a fault can be internal or external to the safety module Internal faults are autonomously detected thanks to its redundant and self monitored structure An external fault can be...

Page 5: ...Should the installer be unable to fully understand the documents the product must not be installed and the necessary assistance may be requested from the manufac turer see paragraph SUPPORT Always at...

Page 6: ...oltage Ui 500 V Minimum duration of input signal 10 ms Input signal filtering yes maximum interference period 0 4 ms Maximum input resistance 100 Maximum input capacitance 470 nF to ground 470 nF betw...

Page 7: ...et tat le module se met dans des conditions de s curit savoir avec toutes les sorties de s curit d sactiv es D faillance une d faillance peut survenir l int rieur ou l ext rieur du module de s curit L...

Page 8: ...une installation et un entretien corrects est dispo nible en ligne en plusieurs langues sur le site de Pizzato Elettrica Cet appareil doit tre install et utilis uniquement si toutes les pr sentes ins...

Page 9: ...ffre R solution 0 1 Hz Temps minimum pour la d tection de l arbre arr t 1 s S paration galvanique oui Tension d isolement Ui 500 V NB Les valeurs de tension et de courant indiqu es se r f rent aux bor...

Page 10: ...ermittelt wird In diesem Status geht das Modul in den Sicherheits Zustand ber d h alle Sicherheits Aus g nge sind deaktiviert Defekt ein Defekt kann intern oder extern am Sicherheits Modul entstehen I...

Page 11: ...st Die Montage und Wartungsanleitungen sind online in verschiedenen Sprachen auf der Webseite von Pizzato Elettrica erh ltlich Das Ger t darf nur installiert und verwendet werden wenn die vorliegende...

Page 12: ...standserkennung 1 s Galvanische Trennung ja Isolationsspannung Ui 500 V NB Die angegebenen Str me und Spannung beziehen sich auf die Versorgungsklemmen Ax je nach Modul unterschiedlich der Platine auf...

Page 13: ...o del m dulo de seguridad cuando se detecta un fallo En este estado el m dulo se pone en el estado de seguridad es decir se desactivan todas las salidas de seguridad Fallo un fallo puede ser interno o...

Page 14: ...dad electromagn tica La documentaci n necesaria para una instalaci n y mantenimiento correctos est disponible en varios idiomas online en el sitio web de Pizzato Elettrica Este dispositivo se debe ins...

Page 15: ...ci n 0 1 Hz Tiempo m nimo para la detecci n de parada del eje 1 s Separaci n galv nica s Tensi n de aislamiento Ui 500 V NB Las tensiones y corrientes indicadas hacen referencia a los bornes de alimen...

Page 16: ...poruchy V tomto stavu se modul p epne do zabezpe en ho stavu tj deaktivuj se v echny bezpe nostn v stupy Porucha porucha bezpe nostn ho modulu m e b t intern nebo extern Intern poruchy jsou zji t ny a...

Page 17: ...e jsou dodr eny a im plementov ny v echny tyto technick pokyny a v echny bezpe nostn p edpisy t kaj c se dan aplikace Pokud instala n technik nedok e pln porozum t dokumentaci instalaci pro duktu pro...

Page 18: ...ly 0 8 V vyp 12 24 V zap Galvanick odd len ano Izola n nap t Ui 500V Minim ln doba vstupn ho sign lu 10 ms Filtrace vstupn ho sign lu Ano maxim ln doba filtrace 0 4 ms Maxim ln vstupn odpor 100 Maxim...

Reviews: