34
ATR 621 - User manual
3
Decimal
Point
Selects type of visualized decimal point.
>
Default
4
Lower Linear Input
AI1 lower limit range, only for linear.
-999…+9999
[digit
4
].
Default
: 0.
5
Upper Linear Input
AI1 upper limit range, only for linear.
-999…+9999
[digit
4
].
Default
: 1000.
6
Off set Calibration
Off set calibration. Number added to visualized process (normally it
corrects ambient temperature value).
-999…+1000
[digit
4
].
Default
: 0.0.
7
Gain
Calibration
Gain calibration. Number multiplied with process value to calibrate
working point.
-99.9%…+100.0
%.
Default
: 0.0.
8
Lower Limit Setpoint
Setpoint lower limit.
-999…+9999
[digit
4
] (degrees.tenths for temperature sensors).
Default
: 0.
9
Upper Limit Setpoint
Setpoint upper limit.
-999…+9999
[digit
4
] (degrees.tenths for temperature sensors).
Default
:
1750.
10
Degree
Select degree type
Centigrade. >
Default
.
Fahrenheit.