30
ATR 621 - User manual
Modbus
address
Description
Read
Write
Reset
value
1013
Error fl ags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold juntion error
Bit3 = Error AI1 (sensor 1)
Bit5 = Generic error
Bit6 = Hardware error
Bit7 = Missing calibration error
Bit8 = Eeprom cycle reading error
RO
0
1014
Cold juntion temperature (degrees with tenth)
RO
-
1200
Cycle selection for remote start
1
= cycle1
…
15
= cycle15
16
= controller
17
= output manual control
R/W
1
1201
Remote Start/Stop (0 = STOP, 1 = START)
R/W
0
1202
Remote setpoint for controller (degrees with
tenths of degree for temperature sensors;
digits for linear sensors).
R/W
0
1203
Remote setpoint for controller with process
decimal point selection.
R/W
0
1204
Remote manual control output percentage
(0-100)
R/W
0
1205
Remote manual control output percentage
(0-1000)
R/W
0
1206
Remote manual control output percentage
(0-10000)
R/W
0
1207
Manual tuning ON/OFF
0
= Tuning off
1
= Tuning on
R/W
0
1210
OFF LINE time* (milliseconds)
R/W
0
2001
Parameter 1
R/W
EEPROM
….
….
R/W
EEPROM
2100
Parameter 100
R/W
EEPROM
4001
Parameter 1**
R/W
EEPROM