9.2
Master and remote setpoint
ATR621-13ABC-T includes a simplifi ed Master mode allowing operation with
other programmers ATR621-13ABC-T or with controllers ATR401-22ABC-T.
Setting
on parameter 77
controller transmits in broadcast (ad-
dress 0) its status (start/stop) and the control setpoint.
Following table shows all data:
Modbus Address
Description
5000
Controllers status:
0
= Controller in stop
1
= Controller during initial waiting
2
= Controller in start
5001
Remote Setpoint
Setting
on parameter 77
controller is normally in stop mode; it
goes in start when the master device on the serial line starts a cycle.
10
Confi guration for installer
To accede confi guration parameters it is necessary to
the controller.
Press
Display
Do
1
PRG
M
Red display shows cycle
selection.
2
Increase until visualize
.
3
OK
On green display appears
with 1st digit fl ashing,
while red display shows
.
*
If it is 0, control is desabled. If it is diff erent from 0, it is “maximum time that can elapse between
two pollings before the controller goes off -line”. If it goes Off -line, the controller goes to Stop
mode.
**
Parameters changed using serial address from 4001 to 4100 are saved in eeprom only after 10’’
after the last writing of parameters.