![Pixsys ATR 621 series User Manual Download Page 41](http://html1.mh-extra.com/html/pixsys/atr-621-series/atr-621-series_user-manual_1560819041.webp)
ATR 621 - User manual
41
53
Alarm 2 State Output
Selects contact type for alarm 2 output.
(Normally Open). >
Default
.
(Normally Closed).
54
Alarm 2 Threshold
Selects setpoint value for alarm 2.
-999…+9999
[digit
4
] (degrees for temperature sensors). >
Default
: 0.
55
Alarm 2 Hysteresis
Selects hysteresis for alarm 2.
-999…+999
[digit
4
] (degrees.tenths for temperature sensors). >
Default
: 1.0.
56
Alarm 2 State Error
Contact satus for alarm 2 output in case of error.
(Open Contact) >
Default
(Contact closed)
57 a.2.Ld. Alarm 2 Led
Defi nes led A2 status corresponding to relevant contact.
(Open Contact)
(Contact closed) >
Default
58
Alarm 2 Action Type
Defi nes alarm 2 action type on operating cycle.
(No Action). Changes only output related to the alarm. >
Default
.
(End Cycle Signal). Cycle ends (STOP) with acoustic and visual
signalling. Changes output related to the alarm, buzzer sounds
and on display fl ashes
until pressing OK.
(Audible Signal). Only acoustic signalling: buzzer sounds.
59
Alarm
3
Alarm 3 selection
(Disabled). >
Default
.
(Absolute Alarm). Referring to the process.
(Band Alarm). Command sepoint ± band.
(High Deviation Alarm). Command se deviation.
(Low Deviation Alarm). Command setpoint - deviation.
(Absolute Command Setpoint Alarm). Reff erring to the sepoint.