ATR 621 - User manual
35
11
Tune
Select autotuning type.
Disabled. >
Default
.
Automatic. Controller checks constantly the process value and
modifi es P.I.D. values (if necessary).
Manual. Started by keys or digital input.
12
Setpoint Deviation Tune
Selects deviation from command setpoint as threshold used by manual
tuning to calculate P.I.D. parameters.
0…5000
[digit
4
] (degrees.tenths for temperature sensors). >
Default
: 5.0.
13
Max Gap Tune
Selects the max. process-setpoint gap, beyond which the automatic tune
recalculates P.I.D. parameters.
1…500
[digit
4
] (degrees.tenths for temperature sensors). >
Default
: 1.0.
14
Minimum Proportional Band
Selects proportional band min. value selectable by automatic tune.
0…9999
[digit
4
] (degrees.tenths for temperature sensors). >
Default
: 5.0.
15
Maximum Proportional Band
Selects proportional band max. value selectable by automatic tune.
0…9999
[digit
4
] (degrees.tenths for temperature sensors). >
Default
: 50.0.
16
Minimum Integral Time
Selects integral time min. value selectable by automatic tune.
0…999.9
seconds. >
Default
: 10.0.
18
Command Action Type
Command output regulation type.
(Heat). Heating regulation (n.o.). >
Default
(Cool). Cooling regulation (n.c.).
19
Command
Hysteresis
Hysteresis in ON/OFF or dead band in P.I.D. for command output.
-999…+999
[digit
4
] (degrees.tenths for temperature sensors). >
Default
: 1.0