25
=
Alarm1 selection (Cooling)
: Proportional band multiplier
: Overlapping / Dead band
: Cycle time Cooling
Parameter
(that ranges from 1.00 to 5.00) determinates the proportio-
nal band for cooling action, according to the formula:
- Proportional band for cooling action
: =
*
In this way it is possible to have a proportional band for cooling action
that will be equal to heating proportional band if
= 1.00, or 5 times
greater if
= 5.00.
- Integral and Derivative time
are the same for both actions.
Parameter
establishes the overlapping (in percentage) betwe-
en the two actions. For installations where heating and cooling outputs
cannot be activated at the same time, a Dead band will be confi gured
(
≤ 0), viceversa an overlapping will be confi gured (
> 0).
Figure below shows an example of double action PID (heating-cooling)
with
= 0 and
= 0.
SPV
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
x
(COOL)
< 0
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
x
(COOL)
= 0
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)