12.15 Alarm Output
Each fast dome has 1 alarm output. A dip switch can program the alarm output for NO (normally open) or
NC (normally close), that can activate the linked devices.
When alarm response mode is set to LOCK Mode:
When the alarm is triggered, NC contact to Common will be open and NO contact to common will
be close. Alarm output will be back to the condition before alarm, 10 seconds after the last alarm is
triggered.
When alarm response mode is set to RELEASE Mode:
When the alarm is triggered, NC contact to Common will be open and NO contact to common will
be close. Alarm output will be back to the condition before alarm, 60 seconds after the last alarm is
triggered.