Wiring
Operating Manual PSEN sg2c
1003267EN02
25
5.10
Single connection
INFORMATION
When the solenoid is operated in singlechannel, only a safety level of PL d
(Cat. 2)/SIL CL 2 can be achieved.
To achieve PL e (Cat. 4/SIL CL 3, the solenoid must have dualchannel op
eration, e. g. via safe pulsed semiconductor outputs with high current load
capacity (0.9 A for 50 ms).
X2-4
24 V
0 V
I1 (ST)
I3 (FS)
A1
A2
PSENsgate
O1 (FS)
Auswertegerät/
Evaluation device/
Appareil de surveillance/
Dispositivo di controllo
FS: Fail-safe
ST: Standard
I4 (FS)
X2-3
X1-3
X1-4
X1-1
X1-2
X1-6
X1-5
I2 (ST)
X1-9
O3 (ST)
X1-8
O2 (FS)
X1-7
5.11
Series connection
CAUTION!
Extension of delayon deenergisation
When several (n) devices are connected in series, the delayon deener
gisation time adds with the number of interconnected safety switches.
The may. delayon deenergisation is composed of
max. delayon deenergisation actuator
+ (n1) x max. delayon deenergisation of the inputs
+ delayon deenergisation of the evaluation device