Safety
Operating Manual PMCprotego S2-2(-C)
1002529-EN-04
10
}
PMCprotego D.48 from Version 1.1
}
PMCprotego D.72 from Version 1.1
3.1.1
Permitted motor types
The following motor types are approved for use with the safety card:
}
Rotary synchronous motors
}
Linear synchronous motors
Please note: The use of synchronous motors without motor encoder (sensorless operation)
is not permitted.
Work is in progress for use with:
}
Asynchronous motors
Please note the following fault detection guidelines:
When the drive is operated with an encoder (standard motor encoder on the servo ampli-
fier), a fault on the encoder system is detected by the safety card as follows:
}
Rotary synchronous motors
Detected within one mechanical revolution of the motor.
}
Linear synchronous motors
Detected within the distance travelled, in accordance with the following formula:
Distance = (Number of poles /2)
·
Pole pair pitch
Commands in the servo amplifier:
–
Number of poles: MPOLES
–
Pole pair pitch: MPITCH
3.1.2
Permitted motor encoder types
The motor encoder is connected to an input on the servo amplifier. The following motor en-
coder types are approved for use with the safety card:
Encoder type
Feedback type (parameter
FBTYPE) in the servo ampli-
fier's commissioning soft-
ware
Connection to the
servo amplifier
Feedback types with one-cable connection (power and feedback in one cable)
Hiperface DSL
35
X1
SFD3
36
X1
Feedback types with two-cable connection (power and feedback in two cables)
Resolver
0
X2
Hiperface (Stegmann)
2
X1
EnDat (Heidenhain)
4
X1
SinCos 5 V with W&S
7
X1
RS422 24V
12
X3
ROD 5 V with Hall
15
X1