Technical data and ordering data
105739_en_04
PHOENIX CONTACT
69
10.3
Conformance with EMC Directive
Maximum duration of the test pulses (when switched on)
3 ms (depending on the load capacity)
Status indicators
One green LED per output
see Section 2.6 “Local diagnostics and status indicators” on page 17
Diagnostics indicators
One red LED per output
see Section 2.6 “Local diagnostics and status indicators” on page 17
Safe digital outputs
WARNING: Loss of safety function
The switch-off pulse can result in the loss of the safety function.
•
Please note that the load on a switch-off pulse (dark test) of 3 ms must not fail or respond in a safety-critical way.
•
Please take this into consideration when selecting the actuator.
WARNING: Loss of safety function
Parasitic voltages can result in the loss of the safety function.
•
Connect the actuator ground to the ground terminal point of the corresponding output on the Axioline F connector. An external ground
may not be used.
•
The connected load must not respond in a hazardous way to test pulses.
Approvals
For the latest approvals, please visit
Conformance with EMC Directive 2014/30/EU
Noise immunity test according to DIN EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2
(IEC 61000-4-2)
Criterion A
6 kV contact discharge, 8 kV air discharge
Electromagnetic fields
EN 61000-4-3
(IEC 61000-4-3)
Criterion A, field strength 10 V/m
Fast transients (burst)
EN 61000-4-4
(IEC 61000-4-4)
Criterion A, test voltage 2 kV
Transient overvoltage (surge)
EN 61000-4-5
(IEC 61000-4-5)
Test intensity 2, Criterion A
DC supply lines:
0.5 kV/0.5 kV (symmetrical/asymmetrical)
Signal lines:
1.0 kV/2.0 kV (symmetrical/asymmetrical)
Conducted disturbance variables
EN 61000-4-6
(IEC 61000-4-6)
Criterion A, test voltage 10 V
Noise emission test according to DIN EN 61000-6-3
Noise emission
EN 55022
Class B, residential
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...