Product description
105739_en_04
PHOENIX CONTACT
17
2.6
Local diagnostics and status indicators
Figure 2-3
Local diagnostics and status indicators
Table 2-1
Overview of diagnostics LEDs
D
Uo
FS
P
00
SD
CM
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
Designation
Color
State
Description
D
Red/yellow/
green
Diagnostics for local bus communication
Green on
The device is ready for operation, communication within the station is OK.
All data is valid. There is no error.
Flashing green
The device is ready for operation, communication within the station is OK.
The data is
not
valid. Valid data from the controller/higher-level network not
available.
There is no error on the module.
Flashing
green/yellow
The device is ready for operation, communication within the station is OK.
Output data
cannot
be output and/or input data
cannot
be read.
There is an error on the I/O side of the module.
Yellow on
The device is ready for operation, but has still not detected a valid cycle
after power on.
Flashing
yellow
The device is not (yet) part of the active configuration.
Red on
The device is ready for operation, but has lost the connection to the bus
head.
Flashing red
The device is ready for operation, but there is no connection to the previous
device.
Off
Device is in (power) reset.
UO
Green
Diagnostics for digital output supply
Green on
Supply for the digital outputs is present and is > around 17 V DC.
Flashing green
Supply for the digital outputs is not present or is < around 17 V DC.
FS
Red
Diagnostics for failure state
Off
The safety application has a valid parameterization.
(Only applies if UO is on or flashing at the same time.)
Red on
Hardware fault. Communication to the higher-level controller is disabled.
The module has entered the safe state (failure state).
Flashing red
The module is not parameterized.
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...
Page 86: ...AXL F PSDO8 3 1F 86 PHOENIX CONTACT 105739_en_04 ...