Ambient compatibility
Not resistant to organic chlorine compounds
Connection data for Axioline F connectors
Connection method
Spring-cage terminal blocks
Conductor cross section
Solid: 0.5 mm
2
to 1.5 mm
2
Flexible without sleeve: 0.25 mm
2
to 1.5 mm
2
Flexible with sleeve: 0.25 mm
2
to 1.5 mm
2
24 - 16 AWG
Supported stop category according to EN 60204
0
1 in error-free state
General data [...]
UL note:
Use copper wire that is approved up to 75°C.
Mechanical requirements
Vibration according to IEC 60068-2-6
10 - 57 Hz: 0.35 mm with constant amplitude
57 - 150 Hz; 5g acceleration, constant amplitude
Shock according to IEC 60068-2-27
30g over 11 ms, Criterion A
Safety characteristic data according to EN 61508
Achievable SIL
SIL 2 (single-channel)
SIL 3 (two-channel)
Depends on the parameterization and wiring: see Section 2.5 “Connection
options for actuators depending on the parameterization” on page 16, see
Section 6 “Connection examples for safe outputs” on page 37
Probability of a dangerous failure on demand by the safety function (PFD)
SIL 2: 1% of 10
-2
, maximum (corresponds to 1 x 10
-4
)
SIL 3: 1% of 10
-3
, maximum (corresponds to 1 x 10
-5
)
Probability of a dangerous failure per hour for the entire module (PFH)
SIL 2: 1% of 10
-6
, maximum (corresponds to 1 x 10
-8
)
SIL 3: 1% of 10
-7
, maximum (corresponds to 1 x 10
-9
)
Depends on the parameterization
Hardware fault tolerance (HFT) of the module
1
Permissible duration of use
20 years, 25 years with a low demand rate
Safety characteristic data according to EN 62061
Achievable SIL claim limit
SILCL = SIL 2 (single-channel)
SILCL = SIL 3 (two-channel)
Depends on the parameterization and wiring: see Section 2.5 “Connection
options for actuators depending on the parameterization” on page 16, see
Section 6 “Connection examples for safe outputs” on page 37
Safe failure fraction (SFF)
99%
Probability of a dangerous failure per hour for the entire module (PFH)
SIL 2: 1% of 10
-6
, maximum (corresponds to 1 x 10
-8
)
SIL 3: 1% of 10
-7
, maximum (corresponds to 1 x 10
-9
)
Depends on the parameterization
Hardware fault tolerance (HFT) of the module
1
Permissible duration of use
20 years, 25 years with a low demand rate
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...
Page 86: ...AXL F PSDO8 3 1F 86 PHOENIX CONTACT 105739_en_04 ...