HOST MODE PROGRAMMING
53
PARAMETER COMPLETE
PATH
SHC
PT
VALUE
AUXILIARY SERIAL PORT / LINE PARAMETERS
Baud Rate
/Comms
/SerAux/Line
/StdBaud
53
1
8 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
6 = 57600
7 = 115200
Parity /Comms
/SerAux/Line
/Parity
54
1
0 = None
1 = Odd
2 = Even
Data Bits
/Comms
/SerAux/Line
/Data
55
1
0 = 7
1 = 8
Stop Bits
/Comms
/SerAux/Line
/Stop
56
1
0 = 1
1 = 2
CBX GATEWAY
Type /Comms
/CBXModuleType
5303
1
0 = None
1 = Profibus
2 = DeviceNet
3 = Ethernet (Ethernet/IP
- TCP/IP)
4 = CC-Link
5 = CANopen
6 = Profinet (Profinet IO
– TCP/IP)
8 = Modbus TCP
(Modbus TCP - TCP/IP)
ETHERNET LINE PARAMETERS
IP Addressing
/Comms
/CBXGateway
/Ethernet/
IPAddressing
95
1
0 = Static Assignment
1 = DHCP
2 = Remote Assignment