PV700a / PV1000a pellet burners
p
28/ 59
DK9401B1 www.pelltech.eu
Modem has two indicators. Green one shows that modem is turned on. Red one shows modem
status. Modem’s statuses are
described in Table 5.
Table 5 Modem statuses
Red LED indicator
Modem status
Permanently on
Sending message (on-going call)
Fast interrupt sequence (period 0,5 s Ton 1s)
Net search/Not registered/ Turning off
Slow interrupt sequence (period 0,3s Ton 3 sec) Registered full service
Permanently off
Device is turned off
3.2 Error output
PV700/PV1000 burner has built in error output what gives 230 VAC tension (NO) to 7-pole socket’s S3
connector or interrupts it (NC) if burner delivers any error message from elven (FLAME ERROR, BATTERY
EMPTY, IGN.ERROR etc). Device (motor, modem etc) up to 5A@230VAC can be connected to circuit.
PAR50 defines weather error output is closed or open during error appearance. Depending on NO or NC
selection values in PAR50 have to be changed.
PAR50 value
Description
1
Normaly open circuit (NO). Switches on when error appears.
2
Normaly closed circuit (NC). Switches off when error appears.
3
SWITCHED ON in IGNITING, HEAT UP, BURNING and HOLD FLAME statuses.
4
Not in use.
5
Not in use.
To insert the SIM card, the modem has to be
disconnected from supply mains. To insert the card
push it into a slot as long as its spring clicks and fixes
the card. See Figure 30. To remove card push it in as
long as spring clicks and pushes it out.
In order to activate SMS sending, in burners menu
PAR52 has to be changed. Value shows for how many
numbers the message will be sent. “0” means no
messages to be sent. “2” means that messages will be
sent to 2 first recipients in SIM card in order of phone
number insertion.
Figure 30 SIM card insertion