PV700a / PV1000a pellet burners
p
35/ 59
DK9401B1 www.pelltech.eu
Table 11 CLEANING parameters
PAR name
PAR No
Value
Unit
Test conditions
CLEANING CYCLE
PAR48
0...250 min
BURNING time between two CLEANING cycles. If set
to 0 then CLEANING is turned off. If BURNING has
been longer than 2x PAR48 set, then extraordinary
cleaning will made.
GRATES CURRENT
PAR47
0.2..6
A
Linear motors maximum current level. If greater, then
motor is stopped and cleaning cycle is started again.
Linear motor’s
min. current
-
0.1
A
If current is smaller, then motor is stopped and
running direction can be changed.
Max. move time
-
58
sec
Maximum time to move actuator to one direction.
Max. cleaning
time
-
100
sec
Maximum CLEANING cycle time.
At the
LOADING
cycle, external auger is turned on. When pellet level in the burner reaches to level
sensors, internal feeder is started. Feeder auger loads necessary amount of fuel needed for ignition into
burning chamber. Amount of loaded fuel is measured by counting the rotations of feeder auger.
LOADING cycle is ended when feeder auger has made exact number of rotations pre-set in PAR24.
Table 12 Loading parameters
PAR
No
Parameter name
Default
value
Unit
Comment
PAR24
LOADING FEED
35..40
rot
Number of feeder auger rotations needed to load
pellets into burning chamber. Depends from burner
model.
PAR25
LOADING 2 FEED
5
rot
Number of feeder auger rotations for second loading.
-
Max loading time
5
min Maximum regular loading time
-
First loading time
after manual start
20
min Maximum loading time after manual start.
-
External auger start
3
sec
Auger Start delay if no fuel in burner
-
External auger stop
3
sec
Auger Stop delay if fuel in burner
-
Feeder auger start
1
sec
Feeder Start delay if fuel in burner
-
Feeder auger stop
4
rot
Feeder rotations made without fuel level before
stopped.
At the
LOADING
time, external auger holds permanent fuel level in the feeder auger’s tube. Depending
on the level sensor signal, the external auger is turned on or off.
Feeder auger’s work depends also on fuel level sensor signal.
Maximum loading time is limited by 20 minutes after manual (initial) start up because extra time for
external auger filling is needed. In next loadings, maximum time is limited by 5 minutes.
If maximum loading time is exceeded and silo selection on burner is used, the pellet delivery will be
switched to other external auger. In single pellet container delivery system NO PELLETS error will occur.