18
5.
Flow Control Valve
: Flow control valves such as the
TACO Flo-Chek or Bell & Gossett Flo-Control™ are
used to prevent gravity circulation by incorporating a
check valve with a weighted disc.
6.
Pressure Reducing Valve
: A pressure reducing valve,
such as the Bell & Gossett B-38 or a TACO #329, is
used in a hydronic system to automatically feed water
to the system whenever pressure in the system drops
below the pressure setting of the valve. These valves
should not be used on glycol systems unless close
supervision of the glycol solution is practiced.
7.
Back Flow Preventer
: A back flow preventer (check
valve) is required by some jurisdictions to prevent water
in the hydronic system from backing up into the city
water supply. This is especially important on systems in
which glycol solution is used as the heating medium.
8.
Pressure Relief Valve
: The boiler pressure relief valve
is shipped in the miscellaneous parts box for field
installation. It is extremely important to install this
device.
The valve is to be installed on the boiler supply pipe
as shown in Figure 4.2. Pipe the discharge of the relief
valve to within 12” of the floor and close to a floor
drain.
Provide piping that is the same size or larger than the
relief valve outlet.
WATER PIPING & CONTROLS
Do not operate this appliance without installing the
pressure relief valve supplied with the boiler or one
with sufficient relieving capacity in accordance with
the ASME Rating Plate on the boiler heat exchanger.
WARNING
Pipe the discharge of the relief valve as close as
possible to the floor and away from high traffic areas.
Pipe the discharge to a floor drain. Failure to do so
may result in personal injury and/or property damage.
CAUTION
Figure 4.1: Piping Symbol Key