46
BOILER CONTROL: INTERNAL WIRING & OPERATION
Parameter
Parameter Description
Unit/Option
Default Option
(128) Prog. Output 4.
Do Not Change Without Factory
Approval.
Select the function for programmable
output 4
0: Disabled
1: Module Pump
2: CH Pump
3: DHW Pump
4: System Pump
5: Cascade Pump
6: Alarm Relay
7: Filling Valve
8: LPG Tank
9: External Igniter
10: Air Damper
17: 3-way Valve CH
18: 3-way Valve DHW
19: 3-way Valve CH (powered
when Idle
20: 3-way Valve DHW (powered
when Idle)
3: DHW Pump
(133) Mod. Pump dT
Set the modulating pump target delta
temperature
°F (°C)
19.8 (11.0)
(134) Mod. Pump Start
Time
Set the modulating pump start up time
sec.
240
(135) Mod. Pump Type
Set the modulating pump model
Linear, Linear Inv.
Linear
(136) Mod. Pump Mode
Set the modulating pump mode
On/Off,
Modulating,
Fixed 20% - 100%
On/Off
(137) Mod. Pump Min Pwr
Set the modulating pump minimum duty cycle %
10
(138) Appliance Type
Set the appliance type
50: PFC-625 (NAT)
51: PFC-750 (NAT)
52: PFC-625 (LP
53: PFC-750 (LP)
Model Dependent
(139) Dair Configuration
Enable/disable the De-Air function
0, 1, 2
1
(107) Anti Legionella Day
Select the day for the anti-legionella cycle
Sunday – Saturday
Sunday
(108) Anti Legionella Hour
Select the time for the anti-legionella cycle
hrs.
1
(205) Frost Protection
Enable Frost Protection
Enabled/Disabled
Enabled
(206) Anti-Legionella
Enable Anti-Legionella Protection
Enabled/Disabled
Enabled
Table 8.J.2.1 (cont.): Settings -> Boiler Settings -> Boiler Parameters
Parameter
Parameter Description
Unit/Option
Default Option
(184) Burner Address
Set the cascade burner address
Stand-alone
Managing
Dep. 1-7
Stand-alone
(72) Permit
EmergencyMode
Enable/disable the cascade emergency mode
yes/no
Yes
(74) Emergency Setpoint
Set the emergency mode setpoint
°F (°C)
158.0 (70.0)
(75) Delay Per Start Next
Mod.
Set the delay time before the next module
is started
sec.
300
(76) Delay Per Stop Next
Mod.
Set the delay time before the next module
is stopped
sec.
120
(142) Delay Quick Start
Next
Set the fast delay time before the next
module is started
sec.
60
(143) Delay Quick Stop
Next
Set the fast delay time before the next module
is stopped
sec.
30
(77) Hyst. Down Start
Module
Set the hysteresis down after which a module
is started
°F (°C)
9.0 (5.0)
(78) Hyst. Up Stop Module
Set the hysteresis up after which a module is
stopped
°F (°C)
7.2 (4.0)
Table 8.J.2.2: Settings -> Boiler Settings -> Module Cascade