68
BOILER DIMENSIONS & RATINGS
12. BOILER DIMENSIONS & RATINGS
41 9/16"
4 1/8"
7 3/4"
24"
LEFT SIDE VIEW
CL - 6"
AIR INLET
27 1/8"
46 1/16"
FRONT VIEW
9 1/4"
3 3/8"
8 1/4"
2 9/16"
24"
7 1/16"
41 11/16"
12 1/16"
14 3/16"
3 7/16"
26 5/8"
REAR VIEW
2" NPT
SUPPLY (OUTLET)
2" NPT
RETURN (INLET)
6" DIA.
EXHAUST VENT
3/4" NPT
DRAIN
3/4"
CONDENSATE
DRAIN
1 1/2" NPT
GAS INLET
CL - 6" AIR INLET
Figure 12.1: Dimensional Drawing – PFC-625 & PFC-750
*Fan speed values may vary depending on menu changes made to compensate for increased exhaust vent length and wind conditions.
Table 12.2: Combustion Air Fan Speeds
SERIES PFC
TM
COMBUSTION AIR FAN SPEEDS
Boiler
Model
Maximum Input
Fuel
Fan Speed*
MBH
kW
Low Power
Ignition
High Power
PFC-625
625
183.2
Natural Gas
2700
3500
7250
LP Gas
2600
7300
PFC-750
750
219.8
Natural Gas
2650
3500
7350
LP Gas
2700
7400
Table 12.1: Boiler Ratings
SERIES PFC
TM
BOILER RATINGS
Series PFC
TM
Boiler
Model
Input
Gross
Output²
Net Water
Ratings¹
Thermal
Efficiency
Minimum
Maximum
MBH
kW
MBH
kW
MBH
kW
MBH
kW
%
PFC-625
125
36.6
625
183.2
612
179.4
532.2
156
97.9
PFC-750
150
43.9
750
219.8
735
215.4
639.1
187.3
98.0
Note: Consult factory before selecting a boiler for installations with unusual piping and/or pickup requirements, such as intermittent system operation, extensive pipe
system, etc.
1. Net water ratings are based on a piping an pickup allowance of 1.15
2. Gross Output and Thermal Efficiency are based on testing in accordance with ANSI/AHRI STANDARD 1500 – 2015 TESTING STANDARD FOR PERFORMANCE
RATING OF COMMERCIAL SPACE HEATING BOILERS and are 3rd Party verified.