OAFE-2000
IO&M Manual
Paragon Controls Incorporated
45
Revision Level 000
Commonly Adjusted Variables
Object Description
Min
Max
Default
R/W
Address
Data
type
Data Value Descriptions
System 1 K-Factor
0.50 2.000
1
W 40013 4
*Note 1
System 2 K-Factor
0.50
2.000
1
W
40019
4
*Note 1
System 3 K-Factor
0.50 2.000
1
W 40025 4
*Note 1
SubSystem K-Factor
0.50
2.000
1
W
40031
4
*Note 1
System 1 Operating Range
0
*Note 2 *Note
2
W 40077 3
System 2 Operating Range
0
*Note 2
*Note 2
W
40085
3
System 3 Operating Range
0
*Note 2
*Note 2
W 40093 3
SubSystem Operating Range
0
*Note 2
*Note 2
W
40101
3
System 1 Number of Samples
1 99 30 W
40103
2
*Note 3
System 1 Sample Interval Time
1
10
1
W
40104
2
*Note 3
System 2 Number of Samples
1 99 30 W
40105
2
*Note 3
System 2 Sample Interval Time
1
10
1
W
40106
2
*Note 3
System 3 Number of Samples
1 99 30 W
40107
2
*Note 3
System 3 Sample Interval Time
1
10
1
W
40108
2
*Note 3
System 1 Fixed Temperature
-99 999 68 W 40115 1
System 2 Fixed Temperature
-99
999
68
W
40118
1
System 3 Fixed Temperature
-99 999 68 W 40121 1
System 1 Low Alarm
0
999999
0
W
40125
3
System 1 High Alarm
0 999999 0
W 40127 3
System 1 Alarm Delay
0
999
0
W
40129
2
System 1 Lockdown
0 20 3 W
40130
3
System 2 Low Alarm
0
999999
0
W
40132
3
System 2 High Alarm
0 999999 0
W 40134 3
System 2 Alarm Delay
0
999
0
W
40136
2
System 2 Lockdown
0 20 3 W
40137
3
System 3 Low Alarm
0
999999
0
W
40139
3
System 3 High Alarm
0 999999 0
W 40141 3
System 3 Alarm Delay
0
999
0
W
40143
2
System 3 Lockdown
0 20 3 W
40144
3
SubSystem Low Alarm
0
999999
0
W
40146
3
SubSystem High Alarm
0 999999 0
W 40148 3
SubSystem Alarm Delay
0
999
0
W
40150
2
Sub System Lockdown
0 20 3 W
40151
3
Lockdown Delay
0
999
10
W
40153
2
System 1 Tagging
0 12 0 W
40197
6
*Note 4
System 2 Tagging
0
12
0
W
40203
6
*Note 4
System 3 Tagging
0 12 0 W
40209
6
*Note 4
SubSystem Tagging
0
12
0
W
40215
6
*Note 4
Δ
P1 Alarm Setpoint
0 99.0 0 W 40273 4
Δ
P2 Alarm Setpoint
0
99.0
0
W
40275
4
Δ
P3 Alarm Setpoint
0 99.0 0 W 40277 4
Δ
P4 Alarm Setpoint
0
99.0
0
W
40279
4
System 1 Temperature Source
1
3
1
W
40699
1 = Fixed, 2 = Variable, 3 = Network
System 2 Temperature Source
1
3
1
W
40700
1 = Fixed, 2 = Variable, 3 = Network
System 3 Temperature Source
1
3
2
W
40701
1 = Fixed, 2 = Variable, 3 = Network
System 1 Alarm Enable
0
1
0
W
40705
2
0 = Disabled, 1 = Enabled
System 2 Alarm Enable
0
1
0
W
40706
2
0 = Disabled, 1 = Enabled
System 3 Alarm Enable
0
1
0
W
40707
2
0 = Disabled, 1 = Enabled
SubSystem Alarm Enable
0
1
0
W
40708
2
0 = Disabled, 1 = Enabled
∆
P1 Alarm Enable
0
2
0
W
40726
2
0 = Off, 1 = Low Trigger, 2 = Hi
∆
P2 Alarm Enable
0
2
0
W
40727
2
0 = Off, 1 = Low Trigger, 2 = Hi
∆
P3 Alarm Enable
0
2
0
W
40728
2
0 = Off, 1 = Low Trigger, 2 = Hi
∆
P4 Alarm Enable
0
2
0
W
40729
2
0 = Off, 1 = Low Trigger, 2 = Hi
Note 1: K-Factor adjustment is done during system balancing to compensate for system effect in MTSE readings.
Note 2: System Operating Range and maximum Operating Range are dependent on numerous, application specific parameters.
Note 3: Number of Samples and Sampling Interval Time effect response rate seen by sensor. Increasing interval time will slow response and increasing number of
samples will increase sample quantity for the rolling average filter.
Note 4: String is 6 register width, 2 characters per register. 12 characters total + null terminator. Example: System 1 Tagging = “AHU-1 SA ” would be 01 10 00
C4 00 06 0C 48 41 2D 55 20 31 41 53 20 20 20 20 46 EA