OAFE-2000
IO&M Manual
Paragon Controls Incorporated
33
Revision Level 000
5.4.
K-Factor Page Shortcut
Touch the K-Factor Button on the Main Screen and the user will be taken to the K-Factor Page. See
Section 5.2.2, K-Factor Section for more details.
5.5. Notification
Page
All warning messages (with the exception of the transducer zero calibration error shown on the Sensor
Data Page) will be displayed on the systems notification page. The Main Screen will show indication
that one or more alarm conditions are present as shown in the image below. An alarm indication is
displayed on the Main Screen per the following sequence listed below:
1. “Notification” button in black text if no alarms or notifications are present.
2. “Notification” button in red text if noncritical alarm is present. List of noncritical alarms:
a. Operating Range Exceeded
b. Firmware Update
c. Analog Output Error (short circuit, open circuit, circuit overload)
3. Red “Alarm” button when a critical alarm is active. List of critical alarms:
a. High Flow Alarm
b. Low Flow Alarm
c.
Δ
P Alarm
d. Zero Offset Error
e. Sensor Acknowledge Error
4. Selecting any one of the buttons mentioned above navigates to the System Notifications page
where all present alarms are displayed.
5. No alarms are latching – if an alarm is cleared the “Notification” button will go back to black text
state.