OAFE-2000
IO&M Manual
Paragon Controls Incorporated
2
Revision Level 000
This signal is scaled and linearized before being displayed and transmitted out as a 4-20mA or 0-
10VDC signal.
The AutoZero option detects and corrects any zero offset caused by large ambient temperature
changes. The Temperature Compensation option compensates the flow and velocity signal for density
changes caused by variations in the process air temperature.
1.3. Specifications
Power Requirements
20 - 28VAC/VDC Supported Protocols
BACnet MS/TP
Modbus RTU Slave
Power Consumption
8.5W, 15.3VA Max Max communication length
4000 ft. (EIA-485)
Protection
Circuit Polarity Protected
Self-Resetting Fuse
Operating Temperature
-20°F to 158°F
(-29°C to 70°C)
Digital Outputs
(2) Open Collector Digital
Outputs
Temperature Compensated Range -4°F to 158°F
(-20°C to70°C)
Digital Inputs
(2) Dry Contact Digital Inputs Storage Temperature
-40°F to 257°F
(-40°C to 125°C)
Analog Outputs
(4) 16-bit Analog Outputs
Field Selectable 0-10V & 4-20mA
Overvoltage and Overcurrent Protected
Enclosure
Impact Resistant Polycarbonate
IP-66, NEMA 4X Rated
Fire Retardant UL 94 V-0
Analog Inputs
(4) 12-bit Analog Inputs
Field Selectable 0-5V, 0-10V & 4-20mA
Dimensions
9.50" L x 5.69" W x 3.56" H
Terminal Blocks
Pluggable Screw Type
16 to 24 AWG
Pressure Connections
1/4" OD Barbed
Brass
Fittings
Accuracy
+/- 0.25% F.S.
1.4. Safety
1.4.1. Electrical Connections
Before any electrical connections are made, ensure the
POWER SWITCH
is in the
OFF
position.
1.4.2. Static Electricity
The circuit board contains components which are susceptible to damage caused by static electrical
discharge. Should it be necessary to remove the circuit board from the enclosure, appropriate
precautions must first be taken to ensure that the operator and the circuit board are at the same
electrical potential.