5.3.1. Sensor Data Page
The Sensor Data Page button will navigate to a page displaying measured values for the number of
transducers in the MTSE. The transducers are in sequential order from (1) to (10) and display the Fan
# tagging, flow, pressure, and status. The Fan # tagging is not set at the Factory and can be entered
here by touching the box area next to the corresponding Sensor # to bring up the keypad. (We
understand the box and font are small, but we are fitting a lot into this mighty package; a stylus or
closed pen works best for this process.)
The number of sensors displayed on this page is the sum of the following:
System 1 Transducer Quantity
System 2 Transducer Quantity
System 3 Transducer Quantity
+1 for Dual OA if set to “On”
∆
P Quantity
The Sensor Data Page can be useful as a check for proper installation or for some basic
troubleshooting of the MTSE.
1) A negative pressure reading indicates reversed tubing to a sensor (other than a very small
negative pressure value from possible zero drift); swap the low and high signal tubing for
that sensor number.
2) S_Err in the Pressure column indicates a “sensor acknowledge error” from an unresponsive
sensor. This could be due to an over pressurized sensor, a faulty sensor or sensor