OAFE-2000
IO&M Manual
Paragon Controls Incorporated
41
Revision Level 000
Object
Object Name (max 32
Char)
Cr
ea
te
Obje
ct
Servic
e
Delete Object
Servic
e
Optional
Properties
Supported
Writeable
Properties
Property Data
Type
Data Value
Description
(State Text)
Multi State
Input-11
System 1 Sensor 1
Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Alarm
3 = Failure
Analog Input-23
System 1 Sensor 2 Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-24
System 1 Sensor 2
Pressure
No
No
• Description
• Eng Units
R REAL
Multi State
Input-12
System 1 Sensor 2
Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Alarm
3 = Failure
/..
../
Analog Input-39
Sub System Sensor 1
Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-40
Sub System Sensor 1
Pressure
No
No
• Description
• Eng Units
R REAL
Multi State
Input-20
Sub System Sensor 1
Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Alarm
3 = Failure
Note:
Sensors # assignment is as follows:
The Analog Input and Multi State Input objects numbers are assigned based on the System # and the Sensor #
within that system. Order of Systems is as follows:
System 1
,
System 2
,
System 3
,
Sub System
,
Differential
Pressure(s)
. Sub System follows the last System in use.
Analog Input-xx
System x Sensor xx Flow
Analog Input-xx
System x Sensor xx Pressure
Multi State Input-xx
System x Sensor xx Status
TABLE 2 – MSV1, MSV2 and MSV3 Engineering Units State_Text List
Multi State
Value-9, 10,
11
1. Standard
Flow
Units
2. Actual Flow
Units
3. Standard
Velocity
Units
4, Actual
Velocity Units
5. Pressure
Units
Engineering
Units
SCFM ACFM SFPM AFPM
In.
W.C.
SCFH L/S Sm/s Am/s Pa
SL/S Am
3/
S
kPa
Sm
3
/S Am
3/
M
mm W.C.
Sm
3
/M Am
3/
HR
Sm
3
/HR