TABLE B – INPUT ENCODING (ADDR. 0006)
BIT
15÷2
1
0
Description
Not used
IN2 Enable
IN1 Enable
TABLE C – OUTPUT ENCODING (ADDR. 0007)
BIT
15÷6
5
4
3
2
1
0
Description Not used Out 6 Enable Out 5 Enable Out 4 Enable Out 3 Enable Out 2 Enable Out 1 Enable
WARNING: bits 15 to 4 are not managed and are always worth 0.
TABLE D – DIVISION VALUE ENCODING AND DECIMALS
ADDRESS
DESCRIPTION
ACCEPTED VALUES
1101
Division values
1 - 2 - 5 - 10 - 20 - 50
1102
Number of decimals
0 - 1 - 2 - 3 - 4
TABLE E - COMMAND REGISTER (ADDR. 0503) / DATA REGISTER (ADDR. 0501÷0502) ENCODING
REGISTER
VALUE
COMMAND REGISTER FUNCTION
DATA REGISTER FUNCTION
0x0001
Semi-automated zero
0x0002
Auto-tare
0x0003
Pre-set tare
Tare value in Data Register MSB and LSB
0x0004
Clear tare
0x0005
Zero calibration (**)
0x0006
Full Scale calibration (**)
Sample weight value in MSB and LSB
0x0007
Data saving in permanent memory
0x0008
Channel switching
Cell channel in Data Register MSB and LSB
(0 = cell channel A, 1 = cell channel B)
0x0009
Weighing execution command
0x3FFF
Output Data Area enabling (*)
(*) The unit’s parameters managed in the Fieldbus Output Data Area are not modified until this
command is executed. Upon unit switch-on, the Output Data Area is completely reset, the master
Fieldbus must read the setting values from the Input Data Area and copy them into the relevant
registers of the Output Data Area; it then must send the enabling command to the Command
Register. Otherwise all the settings adjusted in the Output Data Area would be reset upon switch-on.
(**) This function is only available in case of FREE operation or in case of METRIC operation with
calibration bridge enabled.