Page 55
The output area registers (written by the master and acquired by the unit), shared by all the PROFIBUS,
PROFINET, ETHERCAT, ETHERNET/IP fieldbuses, are listed in the following table.
The registers’ size is 16 bits. The registers written by the master in the output area are read by the unit
at a fixed frequency of 125 Hz (80 Hz in case of PROFIBUS fieldbus).
The size of the Output area configured in the master fieldbus should match with the size configured in
the unit.
OUTPUT DATA AREA
Byte
Register
address
OUTPUT AREA REGISTER
Notes
1-2
0
Command Register
See relevant table.
3-4
1
Data Register (MSB)
INT. value - Most significant word (See relevant table)
5-6
2
Data Register (LSB)
INT. value - Least significant word (See relevant table)
7-8
3
Monitor register
This value is copied in the equivalent register of the input
area.
9-10
4
Set-Point 1, channel A (MSW)
INT. value - Most significant word
11-12
5
Set-Point 1, channel A (LSW)
INT. value - Least significant word
13-14
6
Set-Point 2, channel A (MSW)
INT. value - Most significant word
15-16
7
Set-Point 2, channel A (LSW)
INT. value - Least significant word
17-18
8
Set-Point 3, channel A (MSW)
INT. value - Most significant word
19-20
9
Set-Point 3, channel A (LSW)
INT. value - Least significant word
21-22
10
Set-Point 4, channel A (MSW)
INT. value - Most significant word
23-24
11
Set-Point 4, channel A (LSW)
INT. value - Least significant word
25-26
12
Set-Point 5, channel A (MSW)
INT. value - Most significant word
27-28
13
Set-Point 5, channel A (LSW)
INT. value - Least significant word
29-30
14
Set-Point 6, channel A (MSW)
INT. value - Most significant word
31-32
15
Set-Point 6, channel A (LSW)
INT. value - Least significant word
33-34
16
Set-Point 1, channel B (MSW)
INT. value - Most significant word
35-36
17
Set-Point 1, channel B (LSW)
INT. value - Least significant word
37-38
18
Set-Point 2, channel B (MSW)
INT. value - Most significant word
39-40
19
Set-Point 2, channel B (LSW)
INT. value - Least significant word
41-42
20
Set-Point 3, channel B (MSW)
INT. value - Most significant word
43-44
21
Set-Point 3, channel B (LSW)
INT. value - Least significant word
45-46
22
Set-Point 4, channel B (MSW)
INT. value - Most significant word
47-48
23
Set-Point 4, channel B (LSW)
INT. value - Least significant word
49-50
24
Set-Point 5, channel B (MSW)
INT. value - Most significant word
51-52
25
Set-Point 5, channel B (LSW)
INT. value - Least significant word
53-54
26
Set-Point 6, channel B (MSW)
INT. value - Most significant word
55-56
27
Set-Point 6, channel B (LSW)
INT. value - Least significant word
57-58
28
(*) Weight division value, channel A See relevant table.
59-60
29
(*) Decimals, channel A
See relevant table.
61-62
30
(*) Load cell capacity, channel A
(MSW)
INT. value - Most significant word
63-64
31
(*)Load cell capacity, channel A
(LSW)
INT. value - Least significant word
65-66
32
(*)Load cell sensitivity, channel A
INT. value
67-68
33
(*) Fixed tare, channel A (MSW)
INT. value - Most significant word