Technical Description
Automatic Control
thermos 200 / 300 DC
© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland
Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de
9
Backup heater / heating circuit
T0
Room temp. measured in 1
st
programmer
x0
room temp. setpoint
H0
hysteresis for x0
T5
Duct heater duct temp. or flow temp.
x5
max. duct temp. / flow temp.
H5
hysteresis for x5
x0
Æ
Menu 3 Settings Temperatures
x5
Æ
Menu 9.5 Setup Duct heater
H0
Æ
Menu 9.5 Setup Duct heater
H5
Æ
Menu 9.5 Setup Duct heater
--------------------------------------------------------------------------------------------------------------
Summer/winter bypass
T1
Intake air temperature at the inlet of the unit x4.1
T4max su/wi bypass
T4
Extract air temp.
x4.2
T4min su/wi bypass
H4
hysteresis for x4.1 / x4.2
x4.1
Æ
Menu 9.1.0 Setup Bypass su/wi
Bypass OPEN:
T4 > x4.1
x4.2
Æ
Menu 9.1.0 Setup Bypass su/wi
Bypass OPEN:
T4 < x4.2
In menu 9.1.1 Setup Bypass - motor
Definition of end positions for
CLOSED
(min)
and
OPEN
(max)
--------------------------------------------------------------------------------------------------------------
GHX valve / frost protection brine pump
T2
Outdoor temperature
x2
min. temp. GHX valve OPEN / pump ON
x4
max. temp. GHX valve OPEN / pump ON
H2
hysteresis
for
x2
and
x4
x4
Æ
Menu 9.2.0 Setup GHX valve/brine pump
Valve OPEN / pump ON:
T2 > x4
x2
Æ
Menu 9.2.0 Setup GHX valve/brine pump
Valve OPEN / pump ON:
T2 < x2
----------------------------------------------------------------------------------------------------------------
Plausibility range of the temperatures T0 – T5 -30 ... 95 °C
Setting parameter specifications:
X0
20.0°C
(00,0 ... 35.0°C)
room temperature setpoint
X1
02.0°C
(-10.0 ... 50.0°C)
frost protection start temperature
X2
05.0°C
(00.0 ... 10.0°C)
Tmin GHX valve OPEN
Tmin
brine
pump
ON
X4
25.0°C
(15.0 ... 35.0°C)
Tmax GHX valve OPEN
Tmax
brine
pump
ON
X4.1
24.0°C
(20.0 ... 35.0°C)
Tmax su/wi bypass OPEN
X4.2
18.0°C
(00.0 ... 20.0°C)
Tmin su/wi bypass CLOSED
X5
50.0°C
(20.0 ... 60.0°C)
max. duct temperature / flow temperature
H0
0.5K
(00.0 ... 5.0K)
hysteresis of room temp. setpoint
H1
0.5K
(00.0 ... 5.0K)
hysteresis of frost protection
H2
1.0K
(00.0 ... 5.0K)
hysteresis of GHX valve / brine frost protection
H3
1.0K
(00.0 ... 5.0K)
hysteresis of supply air temperature
H4
1.0K
(00.0 ... 5.0K)
hysteresis (00.0 … 5.0°C)
H5
1.0K
(00.0 ... 5.0K)
hysteresis of duct temperature / flow temperature
min
max
Su/wi bypass
118
222
actual values always depending on specific unit!
Filter interval
30 ... 250 days
Temperature
Night reduction (0.0 ... 5.0K)
Summary of Contents for thermos 200
Page 2: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......