2. System setup menu
The system setup menu is used to make settings that are necessary for the configuration of the system
during the start-up phase.
These settings shall be made by the authorised installer or by the service
staff of Paul Wärmerückgewinnung GmbH.
Improper changes of the parameters offered in this menu
may cause undesirable effects or even incorrect operation of the system. Any customer service proven to
be caused by improper operator actions will be charged. The system setup is always programmed for the
highest configuration whether or not your specific system can use and evaluate all options mentioned
here.
------------------------
|System setup 9.0 |
| |
9 | Enable <-| TA1
0 |>Frost prot. heater < |
1 | Bypass su/wi |
2 | Brine/ground HX ok| TA2
3 | Heat pump |
4 | Solar |
5 | Duct heater |
6 | Buffer-max |
7 | Ventilation steps |
8 | W-setting |
|
↓
↑
|
------------------------
TA5 TA4 TA3
Scroll through the menu items 9.0 to 9.9 using TA4 and TA5, select an item with TA2. Press TA1 to return
to the previous menu.
The menu items Heat pump, Solar and Buffer-max are available for the compakt 350DC series only. The
remaining menu items need the associated equipment installed.
2.1
Menu System setup – Frost prot. 9.0.0
-----------------------
|Frost prot. 9.0.0 |
| <-| TA1
|PTC: yes/no |
|on: T7< -> (x1)°C |
|Hysteresis: (H1)°C |
| | TA2
| |
| -> - + |
-----------------------
TA5 TA4 TA3
Press TA5 to select a value, and TA3 and TA4 to adjust it.
Example:
Adjustment:
on: T7 <
2°C
Hysteresis: 1°C
Frost prot. On: T7 < 1.0 °C
Secondary conditions Frost protection ON:
Frost protection enabled
Thermal cut-out ok*
Flow
sensor
Fz1
ok*
Power
input
Fz1
ok*
Temperature
sensor
T7
plausible
Ventilation
enabled
Ventilation
other
than
0
Summary of Contents for thermos 200
Page 2: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......