User Guidance
Automatic Control Unit
thermos 200 / 300 DC
®
WÄRMERÜCKGEWINNUNG
© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland
Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de
24
XXXDXXXXXX: FAULT
FZ1
FAULT IFZ1
FAULT IFZ4
XXXEXXXXXX: FAULT
FZ4
FAULT IFZ1
FAULT IFZ4
XXXFXXXXXX: FAULT
FZ1
FAULT
FZ4
FAULT IFZ1
FAULT IFZ4
XXXX0XXXXX:
No faults in this group
XXXX1XXXXX: FAULT
FROST
PROTECTION HEATER IS NOT DETECTED
XXXX2XXXXX: FAULT
BACK-UP
DUCT HEATER IS NOT DETECTED
XXXX3XXXXX: FAULT
FROST
PROTECTION HEATER IS NOT DETECTED
FAULT BACK-UP DUCT HEATER IS NOT DETECTED
XXXXX0XXXX:
No faults in this group
XXXXX1XXXX:
FAULT SUMMER-WINTER BYPASS MOTOR
XXXXXX0XXX:
No faults in this group
XXXXXX4XXX:
FAULT FILTER WAS NOT CHANGED
Example:
Error code:
00000140 means: the faults "summer-winter bypass motor" and "filter was not changed" occur at the same time.
Summary of Contents for thermos 200
Page 2: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......