5.2 EQUIPMENT AND FUNCTIONAL SPECIFICATIONS
5.2.1 CR8506-V controller
Front panel
F1.
.
Emergency button with LED (red)
.
Flush-mounted.push-button.for.activating.the.Manual.Emergency.mode..It.enables.access.to.the.system,.with.top.priority,.from.the.
“quiescent.condition”.or.during.an.Automatic.Emergency,.previously.activated.from.an.external.peripheral.unit..The.LED,.which.is.normally.
extinguished,.will.light.up.steadily.in.the.Manual.Emergency.mode.activated.from.the.unit.in.question..If.the.LED.flashes,.this.indicates.
a.Manual.Emergency.status.activated.from.an.emergency.microphone.station.or.a.remote.controller..The.Emergency.button.will.also.be.
used.for.exiting.the.Manual.Emergency..The.push-button.is.controlled.by.the.internal.diagnostics.system.
F2.
.
Emergency microphone
.
Hand-held.microphone.with.Push-to-Talk.(P.T.T.).key,.for.live.emergency.announcements..The.microphone.is.only.operational.in.Manual.
Emergency.conditions.and.has.priority.over.pre-recorded.emergency.messages..The.microphone.capsule.is.controlled.by.the.internal.
diagnostic.system..Use.only.the.microphone.included.in.the.supply,.connected.directly,.without.any.extension.cable,.to.the.XLR.socket.on.
the.front.panel.of.the.CR8506-V.
F3.
.
Graphic DISPLAY
.
Backlit.black-and-white.graphic.display,.128x64.pixels,.for.displaying.the.many.management.windows,.the.contents.of.which.will.vary.
depending.on.the.operating.conditions.of.the.system.(quiescent.or.emergency)..Together.with.the.+/-.knob.and.with.the.multi-purpose.keys,.
it.is.useful.for.navigating.through.the.menus,.for.adjusting.working.parameters.and.for.managing.advanced.functions..It.will.also.display.
all.the.information.required.concerning.Fault,.Disablement.and.Voice.Alarm.Conditions,.that.are.not.all.signalled.by.the.status.LED’s.
Rear panel
R1.
.
POWER switch
.
ON/OFF.switch.of.the.CR8506-V.system..In.the.O.(OFF).position,.the.system.is.switched.off.and.in.the.I.(ON).position.the.system.is.switched.
on..The.switch.affects.only.the.main.230.VAC.power.supply.(see.the.“Power.Supply.and.Earthing”.and.“Safety.Notes”.sections.for.details.
about.safety).
R2.
.
EMERGENCY UNITS
.
Input.for.connecting.remote.emergency.microphone.stations..Use.only.the.PASO.PMB132-V.and/or.PMB132/12-V.microphone.stations..
RJ45.socket.for.connection.with.Cat..5e.SF/UTP.cable.with.a.shielding.braid.and.shielded.STP.connector.(for.details.of.the.connection,.
consult.the.manual.of.the.PASO.11/716.stations)..The.EMERGENCY.UNITS.must.be.connected.to.one.another.in.daisy-chain.fashion:.
each.of.the.two.connecting.lines.A.and.B.can.reach.a.total.length.of.up.to.1.km.
R3.
.
CR8506-V LINK Sockets for connections among CR8506-V controllers (up to 6)
..
.
Connectors.for.connections.among.several.controllers..If.both.LINk.A.and.LINk.B.are.used,.a.redundant.connection.is.achieved.that.keeps.
the.system.in.working.order.even.if.one.of.the.two.links.fails..If.more.than.one.controller.is.installed.on.the.same.rack,.it.is.possible.to.use.
a.single.LINk.(A.or.B)..if.this.is.done,.it.is.necessary.to.de-activate.the.remote.link.test.not.being.used:
.
. o.
Path
:.HOME./.CONFIGURATION./.
set>.BACkGROUND.TEST./.2-Voice.Alarms./.6-Remote.Link.>.Link.Test