5. OPERATING CONDITIONS AND TERMINOLOGY
5.1 GENERAL DEFINITIONS
Following.is.a.list.of.the.signalling.modes.of.the.operating.conditions.of.the.system.and.of.definitions.used.in.the.rest.of.the.manual,.completed.
by.indications.of.a.general.nature:
5.1.1 Signalling of operating conditions
The.
CR8506-V
.system.is.structured.to.signal.the.different.operating.conditions.on.the.basis.of.the.following.definitions:
“Quiescent condition” (ALARM – FAULT – DIS – SYS LEDs extinguished)
Normal.operating.condition,.with.no.current.failures.or.emergencies..This.status.enables.the.sources.of.music.and.voice.to.be.managed.for.
service.announcements.
“Alarm Condition” (ALARM LED illuminated)
This.operating.condition.signals.the.current.presence.of.at.least.one.alarm.signal,.either.pre-recorded.or.live,.on.at.least.one.output.zone..The.
“Alarm.Condition”.can.be.activated.in.the.form.of.an.Automatic.Emergency.from.an.external.peripheral.unit.connected.to.the.Control.Inputs.or.of.
a.Manual.Emergency.through.an.authorised.operator..During.an.“Alarm.Condition”,.the.functions.of.the.music.sources.and.of.the.voice.services.
referred.to.the.quiescent.condition.are.not.operational.
“Fault warning condition” (Led FAULT)
Operating.condition.signalling.the.presence.of.at.least.one.on-going.failure,.detected.by.the.internal.diagnostics.system.causing.the.FAULT.
LED.to.light.up.steadily..
In.the.event.of.failure.of.a.remote.controller,.the.FAULT.LED.will.flash.
.It.is.accompanied.by.an.acoustic.signal.(buzzer).indicating.the.failure..Depending.on.the.causes.of.the.failure,.the.system.may.in.any.case.
perform.the.functions.relating.to.the.“quiescent”.and.“Alarm”.conditions.
“System Fault” (SYS LED illuminated)
This.operating.condition.signals.that.the.system.is.blocked.as.the.result.of.a.temporary.or.permanent.malfunctioning.of.the.CPU,.detected.by.the.
watchdog..It.is.accompanied.by.an.acoustic.signal.(buzzer).indicating.the.failure..During.a.System.Fault,.the.functions.relating.to.the.“quiescent”.
and.“Alarm”.conditions.are.not.operational.
“Disablement condition” (DIS LED illuminated)
This.operating.condition.signals.that.the.Alarm.signals.for.at.least.one.output.zone.have.been.set.to.a.Disablement.condition..The.system.can.
in.any.case.carry.on.the.functions.pertaining.to.the.“quiescent”.condition.for.all.the.zones..and,.only.for.those.zones.that.are.not.disabled,.the.
functions.pertaining.to.the.“Voice.Alarm.Condition”..
“Automatic Emergency” (CONTROL INPUT STATUS Display with zones active)
This.indicates.a.sequence.of.operations.performed.from.an.external.peripheral.unit.connected.to.the.Control.Inputs..Depending.on.how.these.
inputs.are.programmed,.the.“Voice.Alarm.Condition”.or.an.Alarm.Reset.are.activated.
“Manual Emergency” (LED of the EMERGENCY button ON/flashing)
This.procedure.is.performed.by.an.authorised.operator.using.the.manual.controls,.to.activate.VES.sources.or.to.reset.the.Alarms.(Manual.Alarm.
Reset)..The.operations.carried.out.in.the.Manual.Emergency.mode.have.a.higher.priority.than.those.activated.by.an.Automatic.Emergency..
A.CR8506-V.unit.or.an.emergency.unit.on.which.the.EMERGENCY.LED.is.
illuminated
.is.enabled.for.use.for.activating.VES.sources.or.for.
resetting.the.alarms..A.CR8506-V.unit.or.an.emergency.unit.on.which.the.EMERGENCY.LED.is.
flashing
.indicates.that.a.Manual.Emergency.
has.been.activated.from.a.remote.station.
5.1.2 Glossary
Following.is.a.list.of.definitions.of.terms.used.in.this.manual,.completed.by.indications.of.a.general.nature.
“BGM Source”
:.
One.of.the.following.audio.sources.using.the.“Music”.amplification.channel.(BackGround.Music):
-. Audio.source.connected.to.the.AUX.input.
-. Flash.memory.device.containing.*.mp3.files.plugged.into.to.the.front-panel.USB.EXT.socket.
-. Audio.source.connected.to.the.IN.1.input.(Microphone.input),.set.in.the.IN.OFF.mode.
-. Audio.source.connected.to.the.IN.2.input.(Microphone.or.Line.input).set.in.the.IN.OFF.mode.
During.a.“Voice.Alarm.Condition”,.the.BGM.sources.are.not.operational.
“PA Source”
:.
One.of.the.following.audio.sources.using.the.”Voice”.amplification.channel.for.Public.Address.announcements:
-. Source.of.sound.connected.to.the.IN.1.input.(Microphone.input),.set.in.the.ON.or.PRECEDENCE.MODES.
-. Source.of.sound.to.the.IN.2.input.(Microphone.or.Line.input),.set.in.the.ON,.VOX.or.PRECEDENCE.MODES.
-. EMERGENCY.UNIT.in.the.broadcasting.mode,.PAGING.UNITS.
During.a.“Voice.Alarm.Condition”.the.PA.sources.are.not.operational.