52
PA8500-VES System
System Manual | 2014
UK
CR8506-V
|
RT8506-V
8.6 < CONFIGURATION > MENU
Panel. for. selecting. options. pertaining. to. personnel. specifically.
trained. and. authorised. to. use. the. advanced. system. functions.
and. to. modify. the. configuration. parameters. for. starting. and.
maintaining. the. system.. A. password. for. accessing. these.
functions.may.be.added.
The.options.of.the.
CONFIGURATION
.Menu.enable.the.following.management.panels.to.be.accessed:
8.6.1
ACQUIRE IMPEDANCE
.panel.(via.the.
acquire > IMPEDANCE
option)
For.acquiring.and.storing.the.impedance.values.of.the.speaker.unit.lines,.which.is.necessary.for.system.initialisation.and.diagnostics.
8.6.2
SET TOLERANCE
.panel.(via.the.
set > IMP. TOLERANCE
option)
For.setting.the.tolerance.applicable.to.the.line.impedance..When.the.diagnostic.system.detects.impedance.that.is.out.of.tolerance,.a.“Fault.
Warning.Condition”.is.activated.
8.6.3
20KHZ LEVEL SETTINGS
.panel.(via.the.
set > 20KHZ LEVELS
option)
Setting.the.levels.of.the.20.kHz.test.signal.on.the.various.different.audio.channels.
8.6.4
ALARM LEVEL
panel.(via.the.
set > ALARM LEVEL
option)
Panel.for.adjusting.the.output.volume.of.the.VES.sources:.Emergency.Microphones.and.Alarm.Messages.
8.6.5
AMPLIFIER TEST TIME
.panel.(via.the.
set > AMP SET TIME
option)
Setting.the.interval.between.one.PMD.amplifier.test.and.the.next.
8.6.6
.
DISABLEMENT
panel.(via.the.
set > DISABLEMENT
option)
For.disabling,.in.one.or.more.emergency.zones,.the.activity.envisaged.for.an.“Alarm.Condition”.(Voice.Alarm.Condition)..If.at.least.one.zone.is.
set.to.a.“Disablement.Condition”,.the.dedicated.“DIS.”.LED.will.signal.the.existence.of.a.“Disablement.Condition”.
8.6.7
PASSWORD
panel.(via.the.
Password
option)
Panel.for.enabling,.disabling.and.customising.the.password.for.accessing.the.system.service.levels.
8.6.8
BEEP OPERATION
panel.(via.the.
Beep operation
option)
Panel.for.enabling,.disabling.and.customising.the.system.beep.
< SERVICE >
Connection.to.the.SERVICE.menu.for.technical.personnel.having.the.necessary.password..It.is.used.to.change.the.operating.
parameters.of.the.CR8506-V.system,.up-dating.the.firmware.and.servicing.it.
Note:
The settings of the Service Menu are not covered in this Manual.
If.an.access.password.has.been.enabled,.at.the.time.of.configuration.the.
CONFIGURATION ACCESS
.panel.will.be.displayed:
-.enter.the.four-digit.password.then.press.Ok.to.proceed,.
or
-.press.ESC.to.return.to.the.MAIN.page.
The.default.password.is.
3333
.
Once. the. CONFIGURATION. Menu. is. accessed,. all. the. options. illustrated.
earlier. in. the. “AUDIO. SETTING”,. “INSPECTION”. and. “CONFIGURATION”.
menus. will. be. shown,. as. well. as. the. following. new. options. specific. to. the.
CONFIGURATION.menu..Turn.the.knob.to.browse.through.the.options.listed:
•.
acquire > IMPEDANCE
•.
set > IMP. TOLERANCE
•.
set > 20KHZ LEVELS
•.
set > ALARM LEVEL
• set > SPEECH LEVEL
• set> AMP SET TIME
• set> DISABLEMENT
• set > BACKGROUND TEST
• set > CHIME
• report > FAULTS
• report > IMPEDANCE
• status > CONTROL INP.
• test > INDICATORS
INPUT 1
INPUT 2
Firmware Version
Password
Beep operation
<.
SERVICE
.>
• Exit > Logout
Press.Ok.to.select.the.required.item,.or
-.press.ESC.to.return.to.the.MUSIC.panel.
-.press.MENU.to.return.to.the.MAIN.page..
The.characteristics.of.the.specific.panels.of.the.
CONFIGURATION
.Menu.are.illustrated.below..For.the.other.available.options,.refer.to.the.
appropriate.sections.above..
At.the.end.of.the.setup,.log.out.by.selecting.“
Exit> Logout
”.as.described.in.point.8.5.5,.page.51.
Summary of Contents for CR8506-V
Page 2: ......
Page 9: ... System Manual 2014 PA8500 VES System UK CR8506 V RT8506 V 4 CONNECTIONS ...
Page 62: ......
Page 63: ......