Safe Torque Off
8-23
AC30 series Variable Speed Inverter
SS1 Implementation using Safety Control Unit
This Safe Stop 1 (SS1) implementation causes the drive to come to rest in a controlled manner, and STO is actioned after a time delay determined by
the safety delay relay. This conforms to SS1 defined in EN61800-5-2:2007 para 4.2.2.3 c). The example shows wiring and terminal numbering for a
Siemens 3TK2827, but similar products are available from other vendors. Use of this Siemens part does not imply it is suitable for the user’s application.
The user must select and assess appropriate equipment.
Note:
On power-up, the Safety Control Unit outputs are OPEN; thus STO is requested of the inverter. This responds by energising KA1 if both channels
are active and healthy. KA1 is used as a self-check for the reset cycle of the Safety Control Unit. If a reset cannot be achieved due to KA1 being de-
energised, a fault may be present and must be resolved by the user before relying on the STO function. See Fault Operation on page 8-13.
To start the drive:
Ensure the Safety Demand switch is reset (contacts closed). Press the RESET button to ensure the Safety Control Unit is reset; its
contacts to the inverter should close making the STO function inactive. The inverter STO output should then turn OFF. Then press the
DRIVE START button.
To perform operational stop (non STO):
Press the DRIVE STOP button.
Wait for the motor to come to rest.
A2
PE Y33
24VDC
SAFETY
DEMAND
KA1
POWER
SUPPLY
SAFETY CONTROL UNIT
THIS WIRING MUST BE WITHIN THE CONTROL CUBICLE.
KA1
INVERTER STO
RESE
DRIVE
START
DRIVE STOP
X13/02 X12/01
X10/01 X10/03 X10/06
X12/05
X10/02 X10/04 X10/05
X12/06
A1 Y10 Y11 Y12 Y21 Y22
13
47
57
Y34
14
48
58
Summary of Contents for LINKnet AC30P
Page 4: ...AC30 series Variable Speed Inverter...
Page 16: ...2 4 Introduction AC30 series Variable Speed Inverter...
Page 22: ...3 6 Product Overview AC30 series Variable Speed Inverter...
Page 55: ...Installation Control Module 5 17 AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 57: ...Installation Control Module 5 19 AC30 series Variable Speed Inverter PID Control Wiring...
Page 68: ...5 30 Installation Control Module AC30 series Variable Speed Inverter...
Page 82: ...6 14 Associated Equipment Power Stack AC30 series Variable Speed Inverter...
Page 86: ...7 4 Associated Equipment Control Module AC30 series Variable Speed Inverter...
Page 124: ...9 8 The Graphical Keypad AC30 series Variable Speed Inverter...
Page 126: ...10 2 Routine Maintenance Repair AC30 series Variable Speed Inverter...
Page 152: ...A 26 Compliance AC30 series Variable Speed Inverter...
Page 166: ...E 8 Technical Specifications Power Stack AC30 series Variable Speed Drive...
Page 175: ...AC30 series Variable Speed Drive...