3-2
Product Overview
AC30 series Variable Speed Inverter
Power Stack Features
General
Switching Frequency
Minimum 2kHz (default)
Maximum 8kHz
Derating of output current will apply above the default switching frequency.
Output Frequency
Maximum is Switching Frequency divided by 8. This is limited to 590Hz due to export rules.
e.g.
for 2kHz switching frequency it is 2000/8 = 250Hz
Maximum is Switching Frequency divided by 6, in PMAC Motor Closed Loop Control.
If >590Hz is required, please contact your local Parker Sales representative.
Dual Rating
Normal duty (ND)
Heavy duty (HD)
Stack
Protection
Trip Conditions
Output scct: line-to-line & line-to-earth
Overcurrent:
-
Frame K 220% HD current / Stall
-
Frames L, M & N 190% HD current / Stall
Overvoltage & undervoltage
Heatsink over-temperature
Internal over-temperature
Output current imbalance (Frames L, M & N only)
Missing output current sensor
Missing line phase
Motor Thermistor over-temperature (using GPIO option)
Dynamic Brake scct protection (Frame K only)
Current Limit
Adjustable 110% (ND) or 150% (HD) for 60s
180% shock load limit (Heavy Duty – Frame K only)
Inverse Time
Overload Rating
ND - 110% overload for 60s
HD - 180% overload for 3s (Frame K only), 150% overload for 60s
User
Terminals
Line Input
3 AC input terminals L1, L2, L3 (710 stacks only)
Motor Output
3 AC output terminals - M1, M2, M3 (to be used as line supply connections for AFE applications)
PE
2 protective earth terminals
DC Input
2 DC input terminals DC+ and DC-
Brake Output
1 DC output terminal DB to be used in conjunction with DC+ when connecting a Dynamic Brake
Resistor (Frame K only)
Summary of Contents for LINKnet AC30P
Page 4: ...AC30 series Variable Speed Inverter...
Page 16: ...2 4 Introduction AC30 series Variable Speed Inverter...
Page 22: ...3 6 Product Overview AC30 series Variable Speed Inverter...
Page 55: ...Installation Control Module 5 17 AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 57: ...Installation Control Module 5 19 AC30 series Variable Speed Inverter PID Control Wiring...
Page 68: ...5 30 Installation Control Module AC30 series Variable Speed Inverter...
Page 82: ...6 14 Associated Equipment Power Stack AC30 series Variable Speed Inverter...
Page 86: ...7 4 Associated Equipment Control Module AC30 series Variable Speed Inverter...
Page 124: ...9 8 The Graphical Keypad AC30 series Variable Speed Inverter...
Page 126: ...10 2 Routine Maintenance Repair AC30 series Variable Speed Inverter...
Page 152: ...A 26 Compliance AC30 series Variable Speed Inverter...
Page 166: ...E 8 Technical Specifications Power Stack AC30 series Variable Speed Drive...
Page 175: ...AC30 series Variable Speed Drive...