Compliance
A-15
AC30 series Variable Speed Inverter
You should already have planned your cable routes with respect to segregating these cables for EMC compliance.
•
Use the shortest possible motor cable lengths.
•
When connecting multiple motors to a single VSD, use a star junction point for motor cable connections. Use a metal box with
entry and exit cable glands to maintain shield integrity.
•
Keep electrically noisy and sensitive cables apart.
•
Keep electrically noisy and sensitive parallel cable runs to a minimum. Separate parallel cable runs by at least 0.25 metres. For
runs longer than 10 meters, separation should be increased proportionally. For example if the parallel runs were 50m, then the
separation would be (50/10) x 0.25m = 1.25m.
•
Sensitive cables should cross noisy cables at 90
°
.
•
Never run sensitive cables close or parallel to the motor, dc link and braking chopper circuit for any distance.
•
Never run supply, dc link or motor cables in the same bundle as the signal/control and feedback cables, even if they are
screened.
•
Ensure EMC filter input and output cables are separately routed and do not couple across the filter.
Cable Requirements
Power Supply Cable
Cable Type
Unscreened
Segregation
From all other wiring (clean)
Length Limit
Unlimited
External Filter to Inverter Cable
Cable Type
Screened / Armoured
Segregation
From all other wiring (noisy)
Length Limit
0.3m
Screen to Earth
Both ends
Motor Cable
Cable Type
Screened / Armoured
Segregation
From all other wiring (noisy)
Length Limit
50m (up to 300m with an output choke)
Screen to Earth
Both ends
Brake Cable
Cable Type
Screened / Armoured
Segregation
From all other wiring (noisy)
Length Limit
25m
Screen to Earth
Both ends
Signal / Control Cables
Cable Type
Screened
Segregation
From all other wiring (sensitive)
Length Limit
25m
Screen to Earth
Inverter end only
Summary of Contents for LINKnet AC30P
Page 4: ...AC30 series Variable Speed Inverter...
Page 16: ...2 4 Introduction AC30 series Variable Speed Inverter...
Page 22: ...3 6 Product Overview AC30 series Variable Speed Inverter...
Page 55: ...Installation Control Module 5 17 AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 57: ...Installation Control Module 5 19 AC30 series Variable Speed Inverter PID Control Wiring...
Page 68: ...5 30 Installation Control Module AC30 series Variable Speed Inverter...
Page 82: ...6 14 Associated Equipment Power Stack AC30 series Variable Speed Inverter...
Page 86: ...7 4 Associated Equipment Control Module AC30 series Variable Speed Inverter...
Page 124: ...9 8 The Graphical Keypad AC30 series Variable Speed Inverter...
Page 126: ...10 2 Routine Maintenance Repair AC30 series Variable Speed Inverter...
Page 152: ...A 26 Compliance AC30 series Variable Speed Inverter...
Page 166: ...E 8 Technical Specifications Power Stack AC30 series Variable Speed Drive...
Page 175: ...AC30 series Variable Speed Drive...