E-6
Technical Specifications - Power Stack
AC30 series Variable Speed Drive
DC
FED ELECTRICAL RATINGS
Power Supply = 510V - 650V DC average
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Frame
Size
Product Code
530V DC input ratings
620V DC input ratings
Est.
Eff
(%)
Switching
Frequency
(kHz)
nom / max
Output
Current
Derate
(%/kHz)
Motor
Power
(kW)
Output
Current
(A)
Input
Current
(A)
Motor
Power
(hp)
Output
Current
(A)
Input
Current
(A)
K
Normal Duty
(Output Overload Motoring 110% for 60s)
740-4K0315…
160
315
338
250
302
342
98
2 / 8
8.5
740-4K0380…
200
380
420
300
361
408
98
2 / 8
7.7
740-4K0440…
250
440
524
350
414
476
98
2 / 8
8.3
Heavy Duty
(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)
740-4K0315…
132
260
281
200
240
276
98
2 / 8
7.7
740-4K0380…
160
315
338
250
302
342
98
2 / 8
6.9
740-4K0440…
200
380
421
300
361
409
98
2 / 8
7.5
L
Normal Duty
(Output Overload Motoring 110% for 60s)
740-4L0530…
280
530
588
450
520
609
98
2 / 8
8.8
740-4L0590…
315
590
660
500
590
674
98
2 / 8
9.2
Heavy Duty
(Output Overload Motoring 150% for 60s)
740-4L0530…
250
480
524
400
480
541
98
2 / 8
8.3
740-4L0590…
280
530
585
450
520
609
98
2 / 8
8.5
M
Normal Duty
(Output Overload Motoring 110% for 60s)
740-4M0650…
355
650
736
550
650
737
98
2 / 8
8.2
740-4M0700…
400
700
830
600
680
805
98
2 / 8
8.1
Heavy Duty
(Output Overload Motoring 150% for 60s)
740-4M0650…
315
590
656
500
590
671
98
2 / 8
8.5
740-4M0700…
355
650
736
550
640
739
98
2 / 8
8.2
N
Normal Duty
(Output Overload Motoring 110% for 60s)
740-4N0790…
450
790
933
650
770
873
98
2 / 8
8.5
Heavy Duty
(Output Overload Motoring 150% for 60s)
740-4N0790…
400
700
833
600
700
807
98
2 / 8
8.1
Summary of Contents for LINKnet AC30P
Page 4: ...AC30 series Variable Speed Inverter...
Page 16: ...2 4 Introduction AC30 series Variable Speed Inverter...
Page 22: ...3 6 Product Overview AC30 series Variable Speed Inverter...
Page 55: ...Installation Control Module 5 17 AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 57: ...Installation Control Module 5 19 AC30 series Variable Speed Inverter PID Control Wiring...
Page 68: ...5 30 Installation Control Module AC30 series Variable Speed Inverter...
Page 82: ...6 14 Associated Equipment Power Stack AC30 series Variable Speed Inverter...
Page 86: ...7 4 Associated Equipment Control Module AC30 series Variable Speed Inverter...
Page 124: ...9 8 The Graphical Keypad AC30 series Variable Speed Inverter...
Page 126: ...10 2 Routine Maintenance Repair AC30 series Variable Speed Inverter...
Page 152: ...A 26 Compliance AC30 series Variable Speed Inverter...
Page 166: ...E 8 Technical Specifications Power Stack AC30 series Variable Speed Drive...
Page 175: ...AC30 series Variable Speed Drive...