Technical Specifications - Control Module
F-3
AC30 series Variable Speed Drive
REFERENCE OUTPUTS
+10VREF (X11/05), -10VREF (X11/06)
Output Voltage
+10V and -10V
Accuracy
Better than ±0.5%
Output Current
<10mA
Overload / Short
Circuit Protection
Indefinite
DIGITAL INPUTS
DIN1 (X13/02) – DIN3 (X13/04), DIO1 (X12/01) – DIO4 (X12/04)
Conforming to EN61131-2
Nominal Rated Voltage
24V
Operating Range
DIN1, DIN2, DIN3, DIO1, DIO2, DIO2, DIO4:
0-5V dc = OFF, 15-24V dc = ON
(absolute maximum input voltage ±30V dc)
undefined state
15V
5V
0V
24V
ON
OFF
Input Threshold
Typically 10V
Input Impedance
3.3k
Ω
Input Current
7.3mA ± 10% @ 24V
Sample Interval
1ms
DIGITAL OUTPUTS
DIO1 (X12/01) – DIO4 (X12/04), conforming to EN61131-2
Nominal Open Circuit
Output Voltage
24V (minimum 21V)
Rated Output Current
140mA : The total current available is 140mA, either individually or as the sum of all digital outputs and User +24V
Supply.
Overload / Short
Circuit Protection
Indefinite
Summary of Contents for LINKnet AC30P
Page 4: ...AC30 series Variable Speed Inverter...
Page 16: ...2 4 Introduction AC30 series Variable Speed Inverter...
Page 22: ...3 6 Product Overview AC30 series Variable Speed Inverter...
Page 55: ...Installation Control Module 5 17 AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 57: ...Installation Control Module 5 19 AC30 series Variable Speed Inverter PID Control Wiring...
Page 68: ...5 30 Installation Control Module AC30 series Variable Speed Inverter...
Page 82: ...6 14 Associated Equipment Power Stack AC30 series Variable Speed Inverter...
Page 86: ...7 4 Associated Equipment Control Module AC30 series Variable Speed Inverter...
Page 124: ...9 8 The Graphical Keypad AC30 series Variable Speed Inverter...
Page 126: ...10 2 Routine Maintenance Repair AC30 series Variable Speed Inverter...
Page 152: ...A 26 Compliance AC30 series Variable Speed Inverter...
Page 166: ...E 8 Technical Specifications Power Stack AC30 series Variable Speed Drive...
Page 175: ...AC30 series Variable Speed Drive...