ELECTRICAL INSTALLATION
40
ACR7000 Controller Installation Guide
Analog Inputs (- ANI Option)
For controllers with the -ANI option, a removeable16-pin spring-cage connector provides access to eight single-
ended analog inputs, all referencing ground. The analog inputs can also be configured as four differential inputs by
connecting the input signals in pairs (connect to the inputs; do not connect to the grounds.)
Description
Specification
Connector Type
16-Pin Push-in spring cage connector
Manufacturer
Phoenix Contact
Phoenix Part Number
1790548
Connector Locking
Lock and release lever
Wire range
16-24 AWG (0.2 mm² to 1.5 mm²)
Wire strip length
0.4 in (10 mm)
Wire Connection Method
Push-in spring connection
Ferrules without insulating collar
Cross section: 0.25 mm²; Length: 5 mm ... 7 mm
Cross section: 0.34 mm²; Length: 7 mm
Cross section: 0.5 mm²; Length: 8 mm ... 10 mm
Cross section: 0.75 mm²; Length: 8 mm ... 10 mm
Cross section: 1 mm²; Length: 8 mm ... 10 mm
Cross section: 1.5 mm²; Length: 10 mm
Ferrules with insulating collar
Cross section: 0.14 mm²; Length: 8 mm
Cross section: 0.25 mm²; Length: 8 mm ... 10 mm
Cross section: 0.34 mm²; Length: 8 mm ... 10 mm
Cross section: 0.5 mm²; Length: 8 mm ... 10 mm
Cross section: 0.75 mm²; Length: 8 mm ... 10 mm
Summary of Contents for ACR7000 Series
Page 1: ...Effective September 2020 Document Number 88 033593 01A User Guide ACR7000 Controller...
Page 9: ...INTRODUCTION ACR7000 Controller Installation Guide 9 CHAPTER 1 Introduction...
Page 43: ......
Page 44: ...COMMUNICATIONS 44 ACR7000 Controller Installation Guide CHAPTER 4 Communications...
Page 51: ......
Page 52: ...BASIC OPERATION 52 ACR7000 Controller Installation Guide CHAPTER 5 Basic Operation...
Page 58: ...APPENDIX A 58 ACR7000 Controller Installation Guide Appendix A Accessories...