![Parker ACR7000 Series User Manual Download Page 34](http://html2.mh-extra.com/html/parker/acr7000-series/acr7000-series_user-manual_3846060034.webp)
ELECTRICAL INSTALLATION
34
ACR7000 Controller Installation Guide
Input/Output Electrical/Timing Characteristics
GP Inputs 0
−
11, 12
−
23
Description
Min
Max
Units
Turn-on time
--
1
ms
Turn-off time
--
1
ms
Guaranteed on voltage
21
--
VDC
Guaranteed off voltage
--
3
VDC
Maximum forward voltage
--
30
VDC
Maximum reverse voltage
−
30
--
VDC
Forward current
6.3
15
mA
Note:
All parameters are at the connector pin.
Trigger Inputs 24
−
31, 72
−
79
Description
Min
Max
Units
Turn-on time
--
400
ns
Turn-off time
--
400
ns
Guaranteed on voltage
21
--
VDC
Guaranteed off voltage
--
3
VDC
Maximum forward voltage
--
30
VDC
Maximum reverse voltage
−
30
--
VDC
Forward current
6.3
15
mA
Note:
All parameters are at the connector pin.
Propagation delay due to filtering and isolation is ~400 ns, or encoder capture
resolution of +/
−
5 counts at 10 MHz.
GP Outputs 32
−
39
Description
Min
Typical
Max
Units
Turn-on time
--
--
2
ms
Turn-off time
--
--
1
ms
Working voltage
-30
1
--
30
VDC
On-Time voltage
drop (I
L
≤ 10 mA)
--
--
0.4
VDC
On-time voltage
drop (10 mA < I
L
≤
100 mA)
--
--
4.0
VDC
Load current (T
A
≤ 35 °C)
--
--
100
mA
Load current, I
L
(35 °C < T
A
≤ 50 °C)
--
--
80
mA
Short-Circuit trip current
--
200
--
mA
1. The output is not polarity sensitivity and can be controlled regardless of polarity.
Note
: All parameters are at the connector pin.
Summary of Contents for ACR7000 Series
Page 1: ...Effective September 2020 Document Number 88 033593 01A User Guide ACR7000 Controller...
Page 9: ...INTRODUCTION ACR7000 Controller Installation Guide 9 CHAPTER 1 Introduction...
Page 43: ......
Page 44: ...COMMUNICATIONS 44 ACR7000 Controller Installation Guide CHAPTER 4 Communications...
Page 51: ......
Page 52: ...BASIC OPERATION 52 ACR7000 Controller Installation Guide CHAPTER 5 Basic Operation...
Page 58: ...APPENDIX A 58 ACR7000 Controller Installation Guide Appendix A Accessories...