![Parker ACR7000 Series User Manual Download Page 32](http://html2.mh-extra.com/html/parker/acr7000-series/acr7000-series_user-manual_3846060032.webp)
ELECTRICAL INSTALLATION
32
ACR7000 Controller Installation Guide
General Purpose Inputs/Outputs
The 4 Axis Configuration provides 20 general purpose (GP) digital inputs and four digital outputs through two
connections. They are labeled INPUTS (0-11) and INPUTS (24-31) / OUTPUTS (32-35). The 8 Axis Configuration
provides 40 inputs and eight outputs through four connections. The four connectors are labeled INPUTS (0-11),
INPUTS (24-31) / OUTPUTS (32-35), INPUTS (12-23), and INPUTS (72-79) / OUTPUTS (36-39).
The digital inputs and digital outputs are optically isolated from the digital logic. For inputs, current is limited
internally for input voltage control of 24-volt logic. The connectors are 25-pin female, D-subs.
I/O Connector Specification
Description
Specification
Connector Type
25-pin D-sub, 2-row (female socket)
Manufacturer
KYCON or equivalent
KYCON Part Number K42X-B25S/S-A4NJ
I/O Connector —Mating Connector
1
Description
Specification
Connector Type 25-pin, D-sub, 2-row (male connector)
Manufacturer
TE Connectivity AMP Connectors or equivalent
Cable Kit
AMP Part Number
1658659-1includes:
•
1658659-1 connector
•
shield
•
enclosure
•
two jack screws
•
(does not include contacts or ferrules)
Contacts
Crimp style:
TE Connectivity AMP Part Number 166293-1
1
Mating connectors are not provided
Summary of Contents for ACR7000 Series
Page 1: ...Effective September 2020 Document Number 88 033593 01A User Guide ACR7000 Controller...
Page 9: ...INTRODUCTION ACR7000 Controller Installation Guide 9 CHAPTER 1 Introduction...
Page 43: ......
Page 44: ...COMMUNICATIONS 44 ACR7000 Controller Installation Guide CHAPTER 4 Communications...
Page 51: ......
Page 52: ...BASIC OPERATION 52 ACR7000 Controller Installation Guide CHAPTER 5 Basic Operation...
Page 58: ...APPENDIX A 58 ACR7000 Controller Installation Guide Appendix A Accessories...