C-8
Parameter Reference
AC30 series Variable Speed Drive
AFE Start Up Sequence
In order to minimise the potential occurrence of initial current transients when AFE is switched on, an “AFE Start Settings” block was included in the
default macro. It works in conjunction with the following four soft parameters:
-
1943 AFE Current Limit
-
1944 AFE Current Loop P Gain
-
1945 AFE Stack Frequency
-
1946 AFE Default Stack Frequency
AFE Default Macro Setup Parameters
These soft parameters have to be populated with the values that are required for operation in normal running mode, before first start of AFE mode is
attempted!
Start up values are set as constants within the macro, and can only be changed by reprogramming AFE application into the drive. Soft parameter
1946 AFE Default Stack Frequency allows the user to specify if drive should operate (post start up) with its default switching frequency, or with a
different one, as specified in soft parameter 1945.
It is, by default, set that start up is finished after 1.5 seconds since the run command has taken effect.
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...