Fieldbuses
A-37
AC30 series Variable Speed Inverter
Example PLC Configurations
The examples in this section uses the default parameter mapping of the inverter:
Example Using a SIMATIC S7-300 PLC and SIMATIC Manager
1. Create a project
Start
SIMATIC Manager
and create a new project. Right-click on the
project name at the top level and from
Insert New Object
select
SIMATIC 300 Station
.
AC30 Input Mapping Table
PLC Outputs
AC30 Parameter
Data Type
Plugged Modules
000
0627 Comms Control Word
WORD
Output Unsigned16
001
0681 Comms Reference
REAL
Output Real
002
0000
AC30 Output Mapping Table
PLC Inputs
AC30 Parameter
Data Type
Plugged Modules
000
0661 Status Word
WORD
Input Unsigned16
001
0395 Actual Speed Percent
REAL
Input Real
002
0000
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...