The tables below shows the parameters whose default value is dependent on the Power Stack.
Parameter
PNO NONE
3.5 A 400 V 4.5 A 400 V 5.5 A 400 V 7.5 A 400 V 10.0 A 400 V 12.0 A 400 V 16.0 A 400 V 23.0 A 400 V 32.0 A 400 V 38.0 A 400 V 45.0 A 400 V R1
45.0 A 400 V
Brake Resistance
Ohm 251
100
100
100
100
100
100
100
52
52
26
26
17
Brake Rated Power
kW
252
0.11
0.11
0.15
0.22
0.3
0.4
0.55
0.75
1.1
1.5
1.8
2.2
Autotune Ramp Time
274
10
10
10
10
10
10
10
10
10
10
10
10
mras coupling kc
278
14.9874 14.9874
11.5288
6.2448
2.9363
1.7128
2.6526
2.6526
1.314
0.9592
0.7105
0.7105
mras adaptive kc
280
4.3851
4.3851
2.6283
1.5279
0.7514
0.5727
0.6854
0.6854
0.3198
0.3484
0.1792
0.1792
mras adaptive td
s
282
0.1094
0.1094
0.1094
0.1367
0.1367
0.1367
0.276
0.276
0.3036
0.3795
0.506
0.506
mras ls low threshold
Hz
294
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
mras ls high threshold
Hz
295
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
mras adaptive loop bwdt Hz
300
4
4
4
4
4
4
4
3
3
2
2
2
i lim vhz p gain
308
2
2
2
2
2
2
2
2
2
2
2
2
i lim vhz i gain
309
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.3
0.3
0.3
Search Volts
%
314
9
9
9
9
9
9
9
9
9
9
9
10
Search Boost
%
315
40
40
40
40
40
40
40
40
40
15
15
15
Search Time
316
5
5
5
5
5
5
5
10
10
15
15
25
Flying Reflux Time
318
3
3
3
3
3
3
3
3
3
4
4
5
error scaler
%
322
200
200
200
200
200
200
200
200
200
175
175
150
DC Inj Deflux Time
324
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
1
1
1.5
DC Inj Frequency
Hz
325
9
9
9
9
9
9
9
9
9
9
9
6
DC Pulse Time
327
2
2
2
2
2
2
2
2
2
2
2
2
Final DC Pulse Time
328
1
1
1
1
1
1
1
1
1
3
3
3
DC Current Level
%
329
3
3
3
3
3
3
3
2.5
2.5
1.75
1.75
1.25
DC Inj Base Volts
%
331
100
100
100
100
100
100
100
100
100
100
100
75
stb trim limit
Hz
368
1
1
1
1
1
1
1
1
1
0.75
0.75
0.5
Stack Frequency
kHz
412
4
4
4
4
4
4
4
4
4
4
4
3
Deflux Delay
414
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
2.0
auto boost tc
449
0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.3
0.3
0.3
Rated Motor Current
A
455
1.56
1.56
2.88
4.9
6.5
8.4
9.04
14.6
20
27
26.4
38
Motor Power
kW
460
0.75
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18
Power Factor
461
0.71
0.71
0.7
0.78
0.8
0.8
0.8
0.83
0.86
0.87
0.88
0.88
Acceleration Time
486
10
10
10
10
10
10
10
10
10
10
10
20
Deceleration Time
487
10
10
10
10
10
10
10
10
10
10
10
20
Symmetric Time
489
10
10
10
10
10
10
10
10
10
10
10
20
total inertia
kgm² 590
0.0014
0.0014
0.0014
0.0035
0.050
0.0112
0.0176
0.0176
0.0236
0.0603
0.0754
0.0754
Stall Time
907
90
90
90
90
90
90
90
90
90
90
90
90
Max VDC Ripple
V
913
50
50
50
70
70
80
80
85
85
80
80
80
VDC Ripple Trip Delay
914
60
60
60
60
60
60
60
60
60
60
60
30
frame size
986
4
4
4
4
4
4
4
5
5
6
6
7
Nameplate Mag Current A
1550 0.88
0.88
1.65
2.45
3.12
4.03
4.34
6.51
8.16
10.65
10.03
14.44
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...