8-26
Ethernet
AC30 series Variable Speed Inverters
Parameter Name
No.
Path
Default
Range
Units
Writable
PTP Domain
Number
178
7
Setup::Communications::PTP
Parameters::Base
Comms::PTP
0
0 to
127
ALWAY
S
PTP parameter.
Sets the Domain Number of the inverter. A PTP device will only communicate with other PTP devices
that have the same domain number even if it is on the same physical network.
PTP Log Sync Interval
168
1
Setup::Communications::PTP
Parameters::Base
Comms::PTP
-1
-1 to
0
ALWAY
S
PTP parameter.
Sets the Log Sync Interval. See description in section
Advanced Configuration
for more details. This
parameter should be set to the same value on all inverters using PTP.
PTP Priority2
168
6
Setup::Communications::PTP
Parameters::Base
Comms::PTP
128
0 to
255
ALWAY
S
PTP parameter.
Sets the Priority 2 used as part of the process in determining which PTP device becomes the master
clock. See description in section
Advanced Configuration
for more details.
PTP Lock Threshold
168
5
Setup::Communications::PTP
Parameters::Base
Comms::PTP
0.5 us
0.1 us to 100 us us
ALWAY
S
PTP parameter.
Sets the Lock Threshold when the inverter is a slave clock. When the average offset between the slave
clock and the master clock falls below the Lock Threshold then the slave clock is deemed to be
synchronised as indicated by the parameter 1688 PTP Locked. Note that it will take longer for a slave
clock to be deemed synchronised when a smaller threshold is set.
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...